It carries a 220 kA interrupting capacity at 240 V, dropping to 154 kA at 415 V and 121 kA at 440 V — high enough for most secondary distribution fault levels without cascading upstream breakers.
The 100 A rating holds flat through 50 °C; above that, derate to 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C. For a panel that sees 55 °C ambient, you lose 2 A — negligible for most loads, but worth checking if the circuit is already at 98 A continuous.