Skip to main content
Siemens 3VA1110-6EF36-0HC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1110-6EF36-0HC0 SENTRON MCCB, 100 A, 3-Pole

MPN3VA1110-6EF36-0HC0

Siemens SENTRON 3VA1110-6EF36-0HC0, molded case circuit breaker, 3-pole, 100 A rated continuous current Iu, TM240 thermal-magnetic release, 220 kA breaking capacity at 240 V, IP40 front protection.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1110-6EF36-0HC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1110-6EF36-0HC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96 A
Current at 60 °C94 A
Current at 65 °C92 A
Current at 70 °C90 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 690 V17 kA
3VA1110-6EF36-0HC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1110-6EF36-0HC0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1110-6EF36-0HC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1110-6EF36-0HC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1110-6EF36-0HC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

What this MCCB is for

Its 100 A continuous rating and 3-pole construction make it a fit for feeder circuits, main disconnects, or backup protection on 400 V class systems where the interrupting rating at 415 V (154 kA) covers high-fault locations like transformer secondaries or large motor banks.

Breaking capacity across voltage levels

This MCCB carries a 220 kA interrupting rating at 240 V, 154 kA at 415 V, 121 kA at 440 V, and 17 kA at 690 V.

Derating starts at 55 °C (96 A), dropping to 90 A at 70 °C. If the panel runs hot — near a drive cabinet or rooftop installation — the 70 °C figure gives a clear ceiling without guessing.

Integrated accessories and wiring

The auxiliary contact version is 2 form C (changeover) contacts, rated for control circuits up to the insulation voltage of 800 V. No undervoltage release, no ground fault monitoring, no communication module — this is a straightforward line-protection breaker with basic remote-trip capability.

Frequently asked questions

Where can I buy 3VA1110-6EF36-0HC0 and get a price?

This MCCB is available through independent distribution and is quoted to order against an RFQ. Submit a request for current pricing and availability; lead time and stock position are confirmed at quote time.

What is the breaking capacity of this MCCB at 415 V?

The interrupting rating at 415 V is 154 kA. At 240 V it is 220 kA, at 440 V it is 121 kA, and at 690 V it is 17 kA.

What accessories come fitted on this breaker?

It includes a factory-installed shunt trip release (STL) for remote tripping and two auxiliary switches HQ (form C changeover contacts) for status indication. No undervoltage release, ground fault monitoring, or communication module is fitted.

MPN
3VA1110-6EF36-0HC0