Siemens 3VA1110-6EF36-0KC0 SENTRON MCCB, 100 A, 220 kA at 24

MPN3VA1110-6EF36-0KC0

Siemens SENTRON 3VA1110-6EF36-0KC0, molded case circuit breaker, 3-pole, 100 A rated continuous current, TM240 overcurrent release, 220 kA breaking capacity at 240 V, with shunt trip and 2 HQ auxiliary switches.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1110-6EF36-0KC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1110-6EF36-0KC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96 A
Current at 60 °C94 A
Current at 65 °C92 A
Current at 70 °C90 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V121 kA
Breaking capacity at 690 V17 kA
3VA1110-6EF36-0KC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1110-6EF36-0KC0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1110-6EF36-0KC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1110-6EF36-0KC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1110-6EF36-0KC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The TM240 thermal-magnetic overcurrent release handles overloads and short-circuits; the shunt trip (STL) allows remote tripping via a separate control signal. Breaking capacity is the headline number here: 220 kA at 240 V, 154 kA at 415 V, 121 kA at 440 V, and 17 kA at 690 V.

At 55 °C it drops to 96 A, at 60 °C to 94 A, and at 70 °C to 90 A. If the breaker sits near a drive or transformer inside a sealed cabinet, that 90 A at 70 °C is the actual limit; size the upstream conductor accordingly.

Frequently asked questions

Does this breaker include a shunt trip?

Yes, the design of the auxiliary release is a shunt trip (STL), allowing remote tripping. The separate accessory order code for the integrated auxiliary trip is 3VA9688-0BL33.