Switch Disconnector for Isolation Duty
The 125 A Iu rating on the 160 A frame means it handles continuous load up to that current, with headroom in the frame for fault-withstand capability. The 2 kA limited-time rating (at 1 s and 0.5 s) confirms it can survive brief fault currents during upstream breaker coordination, but it does not self-interrupt a fault.
Undervoltage Release and Auxiliaries
The front-terminal busbar connection mates with SENTRON busbar systems for clean, low-profile panel wiring — no lug terminals to torque, which speeds assembly on a DIN-rail or mounting-plate layout. The 70 mm depth and 76.2 mm width match the 3VA MCCB footprint, so it drops into a panel designed for a 3VA breaker without re-spacing the gland plate.