Skip to main content
Siemens 3VA1112-1AA36-0HC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1112-1AA36-0HC0 SENTRON Switch Disconnector, 125

MPN3VA1112-1AA36-0HC0

Siemens SENTRON 3VA1 IEC frame 160 switch disconnector, 3-pole SD100, In=125 A, without overload or short-circuit protection, clamp connection, shunt trip (STL) 12-30 V DC / 24 V AC 50/60 Hz, 2 auxiliary switches HQ.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1112-1AA36-0HC0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
Product versionin MCCB design
3VA1112-1AA36-0HC0 — Ratings
ParameterValue
Number of poles3
Power loss, max.38 W
3VA1112-1AA36-0HC0 — Construction & Connection
ParameterValue
Main circuit connection typeTerminal connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1112-1AA36-0HC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1112-1AA36-0HC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1112-1AA36-0HC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

Switch disconnector for isolation and switching duty

The Siemens 3VA1112-1AA36-0HC0 is a SENTRON 3VA1 IEC frame 160 switch disconnector rated for 125 A continuous current — it isolates and switches loads under load but provides no overload or short-circuit protection, so it pairs with upstream protective devices in a distribution panel. Rated for 690 V AC and 500 V DC, it handles motor feeder isolation, bus coupler duty, or DC load switching in control cabinets where a visible break is required.

At 70 mm deep, 76.2 mm wide, and 130 mm tall, this 3-pole unit fits the standard 3VA1 frame footprint — same depth and width as the 100 A line-protection variant 3VA1010-2ED32-0JA0, so a panel laid out for that breaker accepts this switch disconnector without re-drilling or re-spacing.

Frequently asked questions

Will 3VA1112-1AA36-0HC0 drop into a panel designed for 3VA1010-2ED32-0JA0?

Yes — both share the same 70 mm depth, 76.2 mm width, and 130 mm height, so the switch disconnector fits the same mounting footprint and terminal arrangement without rewiring.

What is the rated continuous current of 3VA1112-1AA36-0HC0?

The rated continuous current Iu is 125 A.

MPN