Siemens 3VA1112-1AA36-0HH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1112-1AA36-0HH0 SENTRON Switch Disconnector, 125A

MPN3VA1112-1AA36-0HH0

Siemens SENTRON 3VA1112-1AA36-0HH0, switch disconnector in MCCB design, 3-pole, In=125 A, 690 V AC / 500 V DC, with shunt trip (STL) 12-30 V DC / 24 V AC, 2 auxiliary switches HQ + 1 trip alarm switch HQ, front terminal connection.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1112-1AA36-0HH0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON

Ratings

3VA1112-1AA36-0HH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C125 A
Current at 45 °C125 A
Current at 50 °C125 A
Current at 55 °C125 A
Current at 60 °C125 A
Current at 65 °C125 A
Current at 70 °C125 A
Power loss, max.38 W

Construction & Connection

3VA1112-1AA36-0HH0 — Construction & Connection
ParameterValue
Main circuit connection typeTerminal connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1112-1AA36-0HH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA1112-1AA36-0HH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1112-1AA36-0HH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.15 000
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens SENTRON 3VA1112-1AA36-0HH0 is a 3-pole switch disconnector in an MCCB-style housing, rated for 125 A continuous at 40 °C through 70 °C ambient — no derating needed across that span. It operates at 690 V AC or 500 V DC, with an 800 V rated insulation voltage. The unit includes a shunt trip release (STL) for 12-30 V DC or 24 V AC, plus two auxiliary switches and one trip alarm switch, all HQ type. Front terminal connections keep wiring accessible in a panel.

The 3VA1 frame measures 130 mm high, 76.2 mm wide, and 70 mm deep — a standard MCCB footprint that fits most DIN-rail or panel-mount enclosures without re-drilling. IP40 on the front face means it is protected against tools and small wires entering the enclosure, suitable for general-purpose industrial panels. The 38 W maximum power loss at full load should be factored into enclosure thermal calculations.

Mechanical service life is rated at 15,000 operating cycles typical — adequate for frequent switching in distribution or machine disconnect applications. The shunt trip release allows remote emergency-off or interlock tripping without an undervoltage release. No communication function is built in; this is a pure disconnect and isolation device.

Frequently asked questions

What is the continuous current rating of 3VA1112-1AA36-0HH0?

It is rated 125 A continuously from 40 °C up to 70 °C ambient, with no derating required across that temperature range.

What auxiliary switches and releases come with this switch disconnector?

It includes two auxiliary switches (HQ) and one trip alarm switch (HQ), plus a shunt trip release (STL) rated for 12-30 V DC or 24 V AC 50/60 Hz.

Where can I buy 3VA1112-1AA36-0HH0?

This part is sourced to order against an RFQ through independent industrial automation distribution. Availability and current pricing are confirmed at quote time.

MPN
3VA1112-1AA36-0HH0