Skip to main content
Siemens 3VA1112-1AA36-0JC0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA1112-1AA36-0JC0 Switch Disconnector, 125

MPN3VA1112-1AA36-0JC0

Siemens SENTRON 3VA series, switch disconnector in MCCB design, 3-pole, In=125 A, without overload or short-circuit protection, shunt trip (STL) 110-127 V DC/AC, 2 auxiliary switches HQ, front terminal connection, IP40 front.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1112-1AA36-0JC0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
Product versionin MCCB design

Ratings

3VA1112-1AA36-0JC0 — Ratings
ParameterValue
Number of poles3
Power loss, max.38 W

Construction & Connection

3VA1112-1AA36-0JC0 — Construction & Connection
ParameterValue
Main circuit connection typeTerminal connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1112-1AA36-0JC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1112-1AA36-0JC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1112-1AA36-0JC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens SENTRON 3VA1112-1AA36-0JC0 is a 3-pole switch disconnector in MCCB design, rated for 125 A continuous current (Iu) and up to 690 V AC / 500 V DC operational voltage. It is built on the 160 A frame and ships with a shunt trip release (STL) for 110–127 V DC/AC, plus two HQ auxiliary switches. The front-terminal clamp connection suits panel wiring where the disconnector is the isolation point rather than a protective device.

What the ratings mean for fit

At 125 A continuous and 690 V AC, this switch disconnector handles motor loads, transformer primaries, or distribution feeders within its frame rating. The absence of overload or short-circuit protection means it is intended as a load-break isolator — upstream protection (a fuse or MCCB) must cover fault interruption. The shunt trip allows remote emergency-off or undervoltage tripping; it operates on 110–127 V DC or AC 50/60 Hz, so verify control voltage matches the coil rating. The 2 HQ auxiliary contacts (form C) provide status feedback to a PLC or indication lamp. Dimensions are 70 mm deep, 76.2 mm wide, 130 mm tall — a standard 3-pole MCCB footprint that fits most DIN-rail or panel-mount enclosures. IP40 on the front means the operator face is protected against tools and small wires; the enclosure itself should provide the overall IP rating for the installation environment. Operating temperature range of -25 °C to +70 °C and storage from -40 °C to +80 °C cover most indoor industrial panels. Maximum power loss of 38 W at full load should be factored into enclosure thermal calculations, especially in sealed cabinets.

Frequently asked questions

What is the closest functional second-source to 3VA1112-1AA36-0JC0?

The 3VA1110-5EE32-0JA0 is a similar SENTRON 3-pole device on the same 160 A frame, but it is a molded case circuit breaker with a TM220 thermal-magnetic release and 100 A rating — it provides overload and short-circuit protection, which this switch disconnector lacks. The 3VA1112-1AA36-0JC0 is a pure isolator with shunt trip and aux switches; the 3VA1110-5EE32-0JA0 includes a trip unit. They share the same footprint (70 x 76.2 x 130 mm) and front-terminal layout, so a panel designed for the breaker can accept the switch disconnector without rewiring, but the protective function differs.

MPN
3VA1112-1AA36-0JC0