Skip to main content
Siemens 3VA1112-1AA42-0AD0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1112-1AA42-0AD0 SENTRON Switch Disconnector, 125

MPN3VA1112-1AA42-0AD0

Siemens SENTRON 3VA1112-1AA42-0AD0, switch disconnector in MCCB design, 4-pole, 125 A rated continuous current, 690 V AC / 600 V DC, busbar connection, front terminals.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1112-1AA42-0AD0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
Product versionin MCCB design

Ratings

3VA1112-1AA42-0AD0 — Ratings
ParameterValue
Number of poles4
Current at 40 °C125 A
Current at 45 °C125 A
Current at 50 °C125 A
Current at 55 °C125 A
Current at 60 °C125 A
Current at 65 °C125 A
Current at 70 °C125 A
Power loss, max.38 W

Construction & Connection

3VA1112-1AA42-0AD0 — Construction & Connection
ParameterValue
Main circuit connection typebusbar connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1112-1AA42-0AD0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA1112-1AA42-0AD0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1112-1AA42-0AD0 — Mechanical
ParameterValue
Height130 mm
Width101.6 mm
Depth70 mm

Product details

Switch disconnector in MCCB form factor

The Siemens 3VA1112-1AA42-0AD0 is a SENTRON switch disconnector built in an MCCB housing — 4-pole, rated for 125 A continuous current (Iu) across the full ambient range from 40 °C to 70 °C with no derating needed per the datasheet. That flat thermal curve simplifies panel design: you size the busbar and enclosure for 125 A at the worst-case ambient, not a derated intermediate value. Rated insulation voltage is 800 V, with maximum operational voltage 690 V AC 50/60 Hz and 600 V DC. The 4-pole configuration handles three-phase plus neutral switching in a single unit, common for main incomers or generator tie-in applications.

Mounting and connection

Main circuit connection is via busbar — front terminal arrangement — so this unit is designed to bolt directly onto a busbar system, not for cable lug termination. Panel builders should plan for busbar stabs or adapter kits; the 101.6 mm width and 70 mm depth fit standard SENTRON 3VA mounting footprints. IP40 on the front face is typical for enclosed distribution boards; no washdown rating, so keep it inside a cabinet. Three auxiliary switches (HQ type) are integrated, giving 3 CO contacts for status feedback to a PLC or indication lamp. No undervoltage release or voltage trigger is fitted on this variant; the auxiliary release slot is empty. A motor drive can be added as an optional extension if remote switching is needed later.

Frequently asked questions

How do I get current pricing and availability for 3VA1112-1AA42-0AD0?

Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels.

What is the rated continuous current of 3VA1112-1AA42-0AD0?

125 A continuous (Iu), and it holds that rating from 40 °C through 70 °C ambient without derating.

What compliance documentation does this brand provide for 3VA1112-1AA42-0AD0?

The evidence does not list specific compliance certificates (RoHS, REACH, UL, IEC) for this order code. Standard SENTRON documentation applies; request the manufacturer's declaration at quote time.

MPN
3VA1112-1AA42-0AD0