Skip to main content
Siemens 3VA1112-1AA42-0HH0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA1112-1AA42-0HH0 Switch Disconnector, 125

MPN3VA1112-1AA42-0HH0

Siemens SENTRON 3VA1112-1AA42-0HH0 switch disconnector, IEC frame 160, 4-pole, 125 A, without overload or short-circuit protection, shunt trip release, 2 aux switches + 1 trip alarm switch.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1112-1AA42-0HH0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON

Ratings

3VA1112-1AA42-0HH0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C125 A
Current at 45 °C125 A
Current at 50 °C125 A
Current at 55 °C125 A
Current at 60 °C125 A
Current at 65 °C125 A
Current at 70 °C125 A
Power loss, max.38 W

Construction & Connection

3VA1112-1AA42-0HH0 — Construction & Connection
ParameterValue
Main circuit connection typebusbar connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1112-1AA42-0HH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA1112-1AA42-0HH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1112-1AA42-0HH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.15 000
Height130 mm
Width101.6 mm
Depth70 mm

Product details

What this part is and what it does

The Siemens 3VA1112-1AA42-0HH0 is a SENTRON switch disconnector in an MCCB-style housing — IEC frame 160, 4-pole, rated for 125 A continuous across the full ambient range from 40 °C to 70 °C. It provides no overload or short-circuit protection; its job is safe isolation and disconnection under load. The shunt trip release (STL) accepts 12–30 V DC or 24 V AC 50/60 Hz for remote tripping, and the auxiliary switch block carries 2 HQ auxiliary switches plus 1 trip alarm switch, giving 3 CO contacts total.

What the 125 A rating means for panel fit

The 125 A rating is flat from 40 °C to 70 °C — no derating curve to manage in a warm enclosure. That makes it a straightforward drop-in for a 125 A feeder or branch disconnect where the load current is known and stable. The front terminals accept busbar connections, so it integrates into a panel bus system without lug adapters. At 70 mm deep, 101.6 mm wide, and 130 mm tall, it occupies the same footprint as a 3VA1 MCCB of the same frame; the 4-pole width is wider than the 3-pole sibling (76.2 mm).

Frequently asked questions

What is the shunt trip voltage range for this switch disconnector?

The shunt trip (STL) operates on 12–30 V DC or 24 V AC 50/60 Hz.

How many auxiliary contacts does this unit have?

It includes 2 auxiliary switches HQ plus 1 trip alarm switch HQ, providing 3 CO contacts total.

Where can I buy 3VA1112-1AA42-0HH0 and how is it quoted?

This part is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time.

MPN
3VA1112-1AA42-0HH0