Skip to main content
Siemens 3VA1112-1AA46-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1112-1AA46-0AA0 SENTRON Switch Disconnector, 125

MPN3VA1112-1AA46-0AA0
Active

Siemens SENTRON 3VA1112-1AA46-0AA0, switch disconnector in MCCB design, 4-pole, 125 A at 40–70 °C, 690 V AC / 600 V DC, front terminal connection.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1112-1AA46-0AA0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON

Ratings

3VA1112-1AA46-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C125 A
Current at 45 °C125 A
Current at 50 °C125 A
Current at 55 °C125 A
Current at 60 °C125 A
Current at 65 °C125 A
Current at 70 °C125 A
Power loss, max.38 W

Construction & Connection

3VA1112-1AA46-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typeTerminal connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1112-1AA46-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1112-1AA46-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1112-1AA46-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.15 000
Height130 mm
Width101.6 mm
Depth70 mm

Product details

What it is and what it does

The Siemens 3VA1112-1AA46-0AA0 is a SENTRON switch disconnector built in an MCCB (moulded-case circuit breaker) form factor — 4-pole, rated 125 A continuously across the full 40–70 °C ambient range, with no derating needed as the panel warms up. It is a pure disconnect device: no overload or short-circuit protection (no trip unit, no undervoltage release), so it serves as a manually operated load-break switch for isolation and maintenance locking. Rated insulation voltage is 800 V, with operating voltages of 690 V AC and 600 V DC — suitable for 400/480 V three-phase panels and 600 V DC bus applications. The front terminal connection accepts cable lugs or busbars, and the IP40 front face keeps dust out of the enclosure cutout.

Panel fit and integration

The 3VA1112-1AA46-0AA0 mounts into a panel cutout for MCCB-style devices. Dimensions: 130 mm height, 101.6 mm width, 70 mm depth — standard for the 3VA1 IEC frame 160 family. The front terminal layout matches the same footprint as other 3VA1 4-pole disconnectors, so a panel wired for a 3VA1112-5EE32-0AA0 will accept this unit without rewiring, provided the auxiliary contact and release options match (this variant carries none). Mechanical service life is 15,000 operating cycles typical — adequate for daily isolation in a production line over many years. Maximum power loss is 38 W at rated current; factor that into enclosure ventilation if the panel is densely packed.

Frequently asked questions

Where can I buy 3VA1112-1AA46-0AA0 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time.

Will 3VA1112-1AA46-0AA0 drop into a panel wired for 3VA1112-5EE32-0AA0?

Yes — same 3VA1 IEC frame 160 footprint, same 4-pole front terminal arrangement. The difference is that the 5EE32 variant includes an electronic trip unit; the 1AA46 is a pure switch disconnector without overload or short-circuit protection. No rewiring needed, but the protection function changes.

MPN
3VA1112-1AA46-0AA0