Skip to main content
Siemens 3VA1112-3EE32-0AA0-ZD00 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1112-3EE32-0AA0-ZD00 Circuit Breaker, 125A, 25kA

MPN3VA1112-3EE32-0AA0-ZD00

Siemens 3VA1 IEC frame 160, breaking capacity class N, 3-pole, line protection TM220, ATFM, In=125A, Icu=25kA @ 415V, overload protection Ir=88A...125A, short-circuit protection Ii=10 x In, nut keeper kit for DC Power OEM in China.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Product details

Overload protection is adjustable via a TM220 thermal-magnetic trip unit: Ir from 88 A to 125 A, so you dial in the continuous current to match the cable or load. Short-circuit protection is fixed at Ii = 10 x In (1250 A), which is typical for line protection where you want fast magnetic trip on hard faults but avoid nuisance tripping on motor inrush.

Same part, different passport — this unit includes a nut keeper kit configured for a DC Power OEM in China. That means the breaker itself is a standard 3VA1 IEC frame 160 device, but the accessory kit and packaging are tailored for that OEM channel.

Integration notes for the panel builder

The 3-pole footprint fits a 160 A frame cutout; plan for 3 x 70 mm² cable terminations on the line and load side. The TM220 trip unit is field-adjustable without removing the cover — just rotate the dials for Ir and Ii.

Frequently asked questions

Where can I buy the 3VA1112-3EE32-0AA0-ZD00 and get a price?

This part is sourced to order against an RFQ through independent distribution. Submit a request for quote (RFQ) to confirm current availability and pricing — no stock or price figures are published here.

What is the breaking capacity of this circuit breaker?

The Icu (ultimate breaking capacity) is 25 kA at 415 V AC, which is class N on the IEC 60947-2 scale — sufficient for most secondary distribution panels and motor control centers.

What overload and short-circuit protection settings does it have?

Overload protection Ir is adjustable from 88 A to 125 A via the TM220 thermal-magnetic trip unit. Short-circuit protection Ii is fixed at 10 x In (1250 A).

MPN
3VA1112-3EE32-0AA0-ZD00