Skip to main content
Siemens 3VA1112-3EE46-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1112-3EE46-0AA0 SENTRON MCCB, 125 A, 4-Pole, 75.6

MPN3VA1112-3EE46-0AA0
Active

Siemens SENTRON 3VA1112-3EE46-0AA0, molded case circuit breaker, 4-pole, 125 A, TM220 release, 75.6 kA at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1112-3EE46-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1112-3EE46-0AA0 — Ratings
ParameterValue
Number of poles4
Current at 45 °C125 A
Current at 50 °C125 A
Current at 55 °C122 A
Current at 60 °C120 A
Current at 65 °C117 A
Current at 70 °C114 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.28.1 W
3VA1112-3EE46-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM220
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VA1112-3EE46-0AA0 — Construction & Connection
ParameterValue
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1112-3EE46-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1112-3EE46-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1112-3EE46-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

The Siemens SENTRON 3VA1112-3EE46-0AA0 is a 4-pole molded case circuit breaker rated 125 A continuous at 45 °C and 50 °C, derating to 114 A at 70 °C — so the thermal curve starts pulling back above 55 °C, which matters if this lands in a non-ventilated enclosure next to other heat sources. Breaking capacity runs 75.6 kA at 240 V, 52.5 kA at 415 V, and 32 kA at 440 V — that covers most North American and European distribution panels, but at 500 V and 690 V it drops to 11.9 kA, so verify the available fault current at the point of installation if you're feeding a 690 V drive.

The 4-pole format handles three-phase plus neutral switching, common for European-style TN-S or TN-C-S systems where the neutral needs isolation. Max power loss of 28.1 W at full load should be factored into enclosure thermal calculations.

Frequently asked questions

Who supplies 3VA1112-3EE46-0AA0 and how is it quoted for volume purchases?

This part is sourced through independent industrial distribution channels. For volume purchases, submit an RFQ — availability and current pricing are confirmed at quote time. No minimum order quantity is implied by the listing, but standard distributor terms apply.

What is 3VA1112-3EE46-0AA0's listed depth?

The depth is 70 mm (2.76 in), which fits standard SENTRON panel cutouts and mounting bases.

What is 3VA1112-3EE46-0AA0's listed width?

The width is 101.6 mm (4 in), matching the standard SENTRON 4-pole MCCB footprint.

What compliance documentation does Siemens provide for 3VA1112-3EE46-0AA0?

As a SENTRON series MCCB, this part carries IEC 60947-2 compliance, UL listing, and CE marking. RoHS and REACH declarations are available from Siemens' documentation portal. The IP40 front protection rating is per IEC 60529.

MPN
3VA1112-3EE46-0AA0