Breaking capacity runs 75.6 kA at 240 V, 52.5 kA at 415 V, and 11.9 kA at 690 V — that's the fault current it can safely interrupt without welding contacts or venting plasma into the panel.
Full 125 A rating holds through 50 °C ambient. Above that it derates linearly: 122 A at 55 °C, 120 A at 60 °C, 117 A at 65 °C, 114 A at 70 °C.