Siemens 3VA1112-3EF32-0DA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1112-3EF32-0DA0 SENTRON MCCB, 125A, 3-Pole, UVR

MPN3VA1112-3EF32-0DA0

Siemens SENTRON 3VA1112-3EF32-0DA0, 3-pole molded case circuit breaker, 125 A rated at 40 °C, 75.6 kA breaking capacity at 240 V, with undervoltage release, line protection design.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1112-3EF32-0DA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11123EF320AA0

Ratings

3VA1112-3EF32-0DA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C125 A
Current at 45 °C125 A
Current at 50 °C125 A
Current at 55 °C122 A
Current at 60 °C120 A
Current at 65 °C117 A
Current at 70 °C114 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.30.6 W

Protection & Trip Unit

3VA1112-3EF32-0DA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1112-3EF32-0DA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1112-3EF32-0DA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1112-3EF32-0DA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1112-3EF32-0DA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

MCCB for line protection with undervoltage release

The Siemens SENTRON 3VA1112-3EF32-0DA0 is a 3-pole molded case circuit breaker (MCCB) designed for line protection. Its TM240 overcurrent release provides thermal-magnetic protection, and the built-in undervoltage release (UVR) trips the breaker when supply voltage drops below a set threshold — critical for preventing motor re-acceleration after a dip or outage. Rated 125 A at 40 °C and carrying 75.6 kA breaking capacity at 240 V, this MCCB handles high fault currents typical of industrial main feeders or large sub-distribution boards.

Breaking capacity across voltage levels

Breaking capacity drops with system voltage: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 11.9 kA at both 500 V and 690 V. The 11.9 kA figure at 690 V is the limiting value for this frame — verify it against the available fault current at the point of installation. Insulation voltage is rated 800 V, so the breaker is electrically suitable for 690 V systems.

Thermal derating and power loss

Current rating holds at 125 A up to 50 °C ambient, then derates linearly: 122 A at 55 °C, 120 A at 60 °C, 117 A at 65 °C, and 114 A at 70 °C. Maximum power loss is 30.6 W — account for this in enclosure thermal calculations, especially in high-density panels. Operating temperature range is -25 °C to 70 °C; storage range is -40 °C to 80 °C.

Panel fit and dimensions

Mounts on a standard DIN rail or direct panel. Dimensions are 130 mm height, 76.2 mm width (3 inches), and 70 mm depth. The 3-pole width is standard for this current class — verify busbar or cable lug spacing against the existing panel layout. No communication function or ground-fault monitoring on this variant.

Frequently asked questions

What is the breaking capacity of 3VA1112-3EF32-0DA0 at 240 V?

The breaking capacity is 75.6 kA at 240 V. At 415 V it is 52.5 kA, at 440 V it is 32 kA, and at 500 V and 690 V it is 11.9 kA.

What does the undervoltage release (UVR) do on this breaker?

The undervoltage release trips the breaker when the supply voltage drops below a set threshold, preventing automatic re-acceleration of motors after a voltage dip or outage. It is a built-in auxiliary release on this variant.

Where can I buy 3VA1112-3EF32-0DA0?

This MCCB is sourced and quoted to order through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time.

MPN
3VA1112-3EF32-0DA0