The 3VA1112-3EF32-0HA0: The 125 A rating holds flat through 50 °C, then derates to 120 A at 55 °C and 112.5 A at 70 °C — useful if the breaker lives near other heat sources in a dense panel. Footprint is 130 mm high, 76.2 mm wide, 70 mm deep, so it fits standard 3-pole MCCB cutouts.
Shunt trip and auxiliary options