Skip to main content
Siemens 3VA1112-3EF32-0KC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1112-3EF32-0KC0 SENTRON MCCB, 125 A, 3-Pole, Line

MPN3VA1112-3EF32-0KC0

Siemens SENTRON 3VA1112-3EF32-0KC0, 3-pole molded case circuit breaker, 125 A rated continuous current, TM240 overcurrent release, line protection version.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1112-3EF32-0KC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1112-3EF32-0KC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C125 A
Current at 45 °C125 A
Current at 50 °C125 A
Current at 55 °C120 A
Current at 60 °C117.5 A
Current at 65 °C115 A
Current at 70 °C112.5 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 690 V10.5 kA
3VA1112-3EF32-0KC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1112-3EF32-0KC0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1112-3EF32-0KC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1112-3EF32-0KC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1112-3EF32-0KC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

Breaking capacity reaches 75.6 kA at 240 V, 52.5 kA at 415 V, and 32 kA at 440 V — figures that define the fault-clearing capability at the point of installation and drive coordination with downstream devices.

Rating and thermal behavior

Derating begins at 55 °C (120 A), dropping to 112.5 A by 70 °C. For a panel that runs warm — say a packed enclosure near a furnace line — that 12.5 A loss between 50 °C and 70 °C is the figure to budget.

Integration and auxiliaries

Front protection is IP40 — sealed against tools and small wires, not washdown. The integrated shunt trip (STL) is ordered separately as 3VA9688-0BL33.

Frequently asked questions

What is the breaking capacity of 3VA1112-3EF32-0KC0?

75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 10.5 kA at 690 V.

Where can I buy 3VA1112-3EF32-0KC0 and how is it quoted?

Sourced through independent distribution channels and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time — no firm stock or price is published here.

Does 3VA1112-3EF32-0KC0 include a shunt trip?

Yes, it is designed with a shunt trip (STL) auxiliary release; the integrated auxiliary trip order code is 3VA9688-0BL33.

MPN
3VA1112-3EF32-0KC0