Skip to main content
Siemens 3VA1112-3EF36-0BC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1112-3EF36-0BC0 SENTRON MCCB, 125 A, 3-Pole, TM24

MPN3VA1112-3EF36-0BC0

Siemens SENTRON 3VA1112-3EF36-0BC0, molded case circuit breaker, 3-pole, 125 A rated continuous current, TM240 overcurrent release, 75.6 kA interrupting at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1112-3EF36-0BC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA1112-3EF36-0BC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C125 A
Current at 45 °C125 A
Current at 50 °C125 A
Current at 55 °C120 A
Current at 60 °C117.5 A
Current at 65 °C115 A
Current at 70 °C112.5 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 690 V10.5 kA

Protection & Trip Unit

3VA1112-3EF36-0BC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240

Construction & Connection

3VA1112-3EF36-0BC0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1112-3EF36-0BC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1112-3EF36-0BC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1112-3EF36-0BC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

Siemens 3VA1112-3EF36-0BC0 SENTRON MCCB — 125 A, 3-Pole, Line Protection

The Siemens 3VA1112-3EF36-0BC0 is a SENTRON molded case circuit breaker (MCCB) rated for 125 A continuous current at 40 °C, holding that rating steady through 50 °C before a gentle thermal derating curve begins — 120 A at 55 °C, 117.5 A at 60 °C, 115 A at 65 °C, and 112.5 A at 70 °C. That means in a warm panel you still get nearly full ampacity; the derate is predictable and linear. Three-pole, line-protection version with a TM240 thermal-magnetic overcurrent release. No trip indicator on the front, no voltage-trip function, no phase-failure detection, and no communication module — this is a straightforward, non-electronic MCCB for standard distribution. The interrupting ratings are 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 10.5 kA at 690 V, which covers most industrial service-entrance and feeder applications. Dimensions: 130 mm high, 76.2 mm wide, 70 mm deep. That 70 mm depth is the key number for panel layout — it fits standard MCCB mounting footprints. IP40 on the front, so it's fine for dry indoor panels but not washdown areas.

Lifecycle & Sourcing

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time. For a critical-spares min/max, this is a fast mover in the 125 A range — keep one on the shelf if your plant runs Siemens MCCBs.

Integration Notes

Mounts in a standard DIN-rail or panel-mount footprint for 3-pole MCCBs. The 76.2 mm width (roughly 3 inches) is the standard 3-pole form factor — no surprises for panel fill factor. Undervoltage release (UVR) is built in as the auxiliary release design; the integrated auxiliary trip uses order code 3VA9608-0BB11. Two auxiliary switches (HQ type) are included for status feedback to the PLC or annunciator. Rated insulation voltage is 800 V, so it's comfortable on 480 V and 600 V class systems. Operating temperature range -25 °C to 70 °C; storage from -40 °C to 80 °C. Latching endurance is 15,000 operations — typical for this class of MCCB in feeder duty.

Frequently asked questions

What are the key interrupting ratings for the 3VA1112-3EF36-0BC0?

75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 10.5 kA at 690 V. That covers most industrial feeder and service-entrance applications.

What is the continuous current rating and how does it derate with temperature?

125 A continuous from 40 °C through 50 °C. At 55 °C it's 120 A, at 60 °C it's 117.5 A, at 65 °C it's 115 A, and at 70 °C it's 112.5 A. The derating curve is gentle and linear.

Where can I buy the 3VA1112-3EF36-0BC0?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

Does the 3VA1112-3EF36-0BC0 include an undervoltage release?

Yes, the undervoltage release (UVR) is built in as the auxiliary release design. The integrated auxiliary trip uses order code 3VA9608-0BB11.

MPN
3VA1112-3EF36-0BC0