Skip to main content
Siemens 3VA1112-3EF36-0HC0 — Molded Case Circuit Breakers (MCCB)

3VA1112-3EF36-0HC0 SENTRON MCCB, 125 A, 75.6 kA at 240 V

MPN3VA1112-3EF36-0HC0

SENTRON 3VA1112-3EF36-0HC0, molded case circuit breaker, 3-pole, 125 A at 40 °C, breaking capacity 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, 11.9 kA at 500/690 V, line protection design with shunt trip and 2 auxiliary switches.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1112-3EF36-0HC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11123EF360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA1112-3EF36-0HC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C125 A
Current at 45 °C125 A
Current at 50 °C125 A
Current at 55 °C122 A
Current at 60 °C120 A
Current at 65 °C117 A
Current at 70 °C114 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.28.1 W

Protection & Trip Unit

3VA1112-3EF36-0HC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1112-3EF36-0HC0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1112-3EF36-0HC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1112-3EF36-0HC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1112-3EF36-0HC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The SENTRON 3VA1112-3EF36-0HC0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection in distribution panels. It carries 125 A continuously at 40 °C, with the full thermal rating holding through 50 °C before a gentle derate begins — 122 A at 55 °C, 120 A at 60 °C, 117 A at 65 °C, 114 A at 70 °C. That means it can feed a 125 A bus in a warm enclosure without losing headroom.

Breaking capacity and selectivity

The interrupting ratings cover the common industrial voltages: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 11.9 kA at both 500 V and 690 V. At 415 V three-phase — the standard for many European and Asian plants — a 52.5 kA SCCR gives solid fault isolation without cascading upstream. The 800 V rated insulation voltage confirms the internal clearance is sized for 690 V distribution.

Auxiliaries and release configuration

This variant ships with a shunt trip (STL) release and 2 HQ auxiliary switches built in. The shunt trip allows remote tripping from a safety relay or emergency-stop circuit, while the HQ aux contacts report breaker position back to a PLC or status lamp. No undervoltage release, no ground-fault module, no communication function — it is a straightforward line-protection MCCB with remote trip capability.

Physical fit and panel integration

The breaker measures 130 mm high, 76.2 mm wide, 70 mm deep — a 3-pole MCCB footprint that drops into standard SENTRON panel-mounting cutouts. The 70 mm depth keeps it within typical enclosure depth limits for wall-mounted distribution boards.

Frequently asked questions

How do I get current pricing and availability for 3VA1112-3EF36-0HC0?

Submit an RFQ through this listing. We source and quote to order; availability and current pricing are confirmed at quote time through our distribution channels.

What is the breaking capacity of 3VA1112-3EF36-0HC0 at 415 V?

52.5 kA at 415 V, which covers most industrial fault-current scenarios at that voltage level.

Does 3VA1112-3EF36-0HC0 include a shunt trip?

Yes, it ships with a shunt trip (STL) release and 2 HQ auxiliary switches for remote tripping and status feedback.

MPN
3VA1112-3EF36-0HC0