Line protection MCCB with TM240 thermal-magnetic release
Its 125 A rated continuous current (Iu) holds flat from 40 °C to 50 °C, then derates to 112.5 A at 70 °C; if the panel ambient runs hot, that 70 °C figure is the one that governs the real load you can pass through it. Interrupting capacity steps with system voltage: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 10.5 kA at 690 V. For a 480 V distribution panel (common in North American industrial), the 440 V figure is the closest proxy — 32 kA SCCR headroom covers most transformer-fed secondary buses. The TM240 thermal-magnetic release provides fixed short-circuit and overload protection; no communication, no ground-fault module, no auxiliary contacts on this variant.
Shunt trip and auxiliary release
No undervoltage release, no auxiliary contact block on this build. If the BOM calls for remote undervoltage protection or status feedback, the base breaker won't deliver it without adding the separate module.