Skip to main content
Siemens 3VA1112-3GF42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1112-3GF42-0AA0 SENTRON MCCB, 125 A, 4-Pole, 75.6

MPN3VA1112-3GF42-0AA0
Active

Siemens SENTRON 3VA1112-3GF42-0AA0, molded case circuit breaker, 125 A, 4-pole, 75.6 kA interrupting at 240 V, line protection, TM240 release, IP40 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1112-3GF42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA1112-3GF42-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C125 A
Current at 45 °C125 A
Current at 50 °C125 A
Current at 55 °C122 A
Current at 60 °C120 A
Current at 65 °C117 A
Current at 70 °C114 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.28.1 W
3VA1112-3GF42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1112-3GF42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1112-3GF42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1112-3GF42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1112-3GF42-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

Siemens 3VA1112-3GF42-0AA0 — SENTRON MCCB, 125 A, 4-Pole

Per the datasheet, interrupting capacity reaches 75.6 kA at 240 V, 52.5 kA at 415 V, and 32 kA at 440 V — these figures govern the available fault current the breaker can safely clear without upstream cascade. Current derating is documented across the operating range: the breaker carries its full 125 A from 40 °C through 50 °C, then steps down to 122 A at 55 °C, 120 A at 60 °C, 117 A at 65 °C, and 114 A at 70 °C. For a panel builder, that means the 50 °C threshold is the practical limit for nameplate rating — above that, the load must be reduced per the thermal curve. Maximum power loss is 28.1 W, which factors into enclosure thermal calculations. Physical dimensions are 130 mm height, 101.6 mm width, and 70 mm depth. Rated insulation voltage is 800 V, with operating temperature range from -25 °C to 70 °C and storage from -40 °C to 80 °C.

The 4-pole form factor occupies roughly 102 mm of rail width — plan for that footprint plus side clearance for busbar connections and cable bending radius. No communication function or auxiliary voltage trigger is fitted on this base variant; if remote signaling is needed, the 3VA family accepts plug-in accessory modules (shunt trip, auxiliary contacts) that slot into the breaker side.

Frequently asked questions

What are the interrupting capacity ratings for the 3VA1112-3GF42-0AA0?

The interrupting capacity is 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 11.9 kA at both 500 V and 690 V. These values determine the maximum fault current the breaker can safely clear at each voltage level.

Where can I buy the 3VA1112-3GF42-0AA0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment.

What is the thermal derating curve for the 3VA1112-3GF42-0AA0?

The breaker carries its full 125 A from 40 °C through 50 °C. Above that, it derates to 122 A at 55 °C, 120 A at 60 °C, 117 A at 65 °C, and 114 A at 70 °C. The 50 °C threshold is the practical limit for nameplate rating.

What are the physical dimensions of the 3VA1112-3GF42-0AA0?

Height is 130 mm, width is 101.6 mm, and depth is 70 mm. The front face is rated IP40 for protection against solid objects and tools.

MPN