Skip to main content
Siemens 3VA1112-4ED12-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1112-4ED12-0AA0 SENTRON MCCB, 125 A, 1-Pole, TM21

MPN3VA1112-4ED12-0AA0
Active

Siemens SENTRON 3VA1112-4ED12-0AA0, molded case circuit breaker, 1-pole, 125 A, TM210 thermal-magnetic release, 75.6 kA interrupting at 240 V.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1112-4ED12-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA1112-4ED12-0AA0 — Ratings
ParameterValue
Number of poles1
Current at 45 °C125 A
Current at 50 °C125 A
Current at 55 °C122 A
Current at 60 °C120 A
Current at 65 °C117 A
Current at 70 °C114 A
Switching capacity classS
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V9 kA
Power loss, max.9.37 W

Protection & Trip Unit

3VA1112-4ED12-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout

Construction & Connection

3VA1112-4ED12-0AA0 — Construction & Connection
ParameterValue
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1112-4ED12-0AA0 — Accessories & Functions
ParameterValue
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0

Environmental

3VA1112-4ED12-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1112-4ED12-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width25.4 mm
Depth70 mm
Height (in)5.12 in
Width (in)1 in
Depth (in)2.76 in

Product details

What the ratings mean for fit

The Siemens 3VA1112-4ED12-0AA0 is a 1-pole SENTRON molded case circuit breaker rated for 125 A continuous at 45 °C and 50 °C, derating to 114 A at 70 °C. The TM210 thermal-magnetic release provides fixed LI protection — the instantaneous trip (Ii) is fixed at 1250 A, ten times the continuous rating, which gives good inrush headroom for motor or transformer branch circuits without nuisance tripping on startup. Interrupting capacity is 75.6 kA at 240 V AC and 9 kA at 415 V AC — the 240 V figure covers most North American panelboard applications, while the 415 V rating suits IEC distribution where fault currents are lower. The 1-pole format fits standard 25.4 mm (1 in) per-pole width on DIN rail, matching the SENTRON 3VA family footprint for easy retrofit or new build.

Integration and deployment

Mounts on DIN rail in a standard enclosure with IP40 protection on the front face — suitable for dry indoor panel environments. The 70 mm depth (2.76 in) leaves clearance behind the door for wiring and auxiliary accessories. No communication function or motor drive option is fitted on this variant; it is a standalone line-protection breaker.

Frequently asked questions

How do I get current pricing and availability for 3VA1112-4ED12-0AA0?

We source this part to order against an RFQ; availability and current pricing are confirmed at quote time through our independent distribution network.

What is the interrupting rating of 3VA1112-4ED12-0AA0 at 240 V?

75.6 kA at 240 V AC, and 9 kA at 415 V AC — the 240 V figure covers most North American panelboard applications.

What compliance documentation does Siemens provide for 3VA1112-4ED12-0AA0?

The part carries IEC 60947-2 design and is marked with reference code Q per IEC 81346-2. Full compliance documentation (RoHS, REACH, UL file) is available from Siemens on request.

MPN
3VA1112-4ED12-0AA0