Skip to main content
Siemens 3VA1112-4EF32-0HH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1112-4EF32-0HH0 SENTRON MCCB, 125 A, 3-Pole, 121

MPN3VA1112-4EF32-0HH0

Siemens SENTRON 3VA1112-4EF32-0HH0, molded case circuit breaker, 3-pole, 125 A, TM240 release, 121 kA at 240 V, line protection.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1112-4EF32-0HH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1112-4EF32-0HH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C125 A
Current at 45 °C125 A
Current at 50 °C125 A
Current at 55 °C120 A
Current at 60 °C117.5 A
Current at 65 °C115 A
Current at 70 °C112.5 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 690 V11.9 kA
3VA1112-4EF32-0HH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1112-4EF32-0HH0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1112-4EF32-0HH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1112-4EF32-0HH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1112-4EF32-0HH0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

It's a 3-pole line-protection device built for distribution panels where high interrupting capacity is the deciding spec — 121 kA at 240 V, 75.6 kA at 415 V, and still 11.9 kA at 690 V. That kind of SCCR headroom means it can sit upstream of a fault-heavy feeder without cascading, which is what you want when coordinating a main breaker with downstream branch devices. The TM240 release is a fixed thermal-magnetic trip — no interchangeable rating plug, so the 125 A frame is what you get. That's fine for a dedicated feeder or a fixed-load panel where the ampacity isn't changing.

At 70 mm deep, 76.2 mm wide, and 130 mm tall, this MCCB fits the standard SENTRON 3VA footprint. The 76.2 mm width is a 3-module (3 x 25.4 mm) DIN-rail pitch — it snaps onto the rail without adapters.

Frequently asked questions

What is 3VA1112-4EF32-0HH0's interrupting capacity at 415 V?

It's rated at 75.6 kA at 415 V. That's the figure you'd use for most European 400 V distribution panels.

Where can I buy 3VA1112-4EF32-0HH0?

This MCCB is sourced to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

Does 3VA1112-4EF32-0HH0 include auxiliary contacts?

Yes, it comes with 2 auxiliary switches plus 1 trip alarm switch (HQ configuration), wired and ready for status feedback.

What is the rated continuous current of 3VA1112-4EF32-0HH0 at 40 °C?

125 A continuous at 40 °C. The unit derates to 112.5 A at 70 °C ambient.

MPN
3VA1112-4EF32-0HH0