Skip to main content
Siemens 3VA1112-4EF36-0AF0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1112-4EF36-0AF0 SENTRON MCCB, 125A, 121kA at 240V

MPN3VA1112-4EF36-0AF0

Siemens SENTRON 3VA1 molded case circuit breaker, 3VA1112-4EF36-0AF0, 3-pole, 125 A at 40 °C, 121 kA breaking capacity at 240 V AC, TM240 thermal-magnetic release, line protection design.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1112-4EF36-0AF0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11124EF360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA1112-4EF36-0AF0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C125 A
Current at 45 °C125 A
Current at 50 °C125 A
Current at 55 °C122 A
Current at 60 °C120 A
Current at 65 °C117 A
Current at 70 °C114 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 500 V11.9 kA
Breaking capacity at 690 V11.9 kA
Power loss, max.28.1 W

Protection & Trip Unit

3VA1112-4EF36-0AF0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1112-4EF36-0AF0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1112-4EF36-0AF0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1112-4EF36-0AF0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1112-4EF36-0AF0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

What it is and what it does

The Siemens SENTRON 3VA1112-4EF36-0AF0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection in distribution panels. It carries a continuous current rating of 125 A at 40 °C, with minimal thermal derating up to 70 °C — still delivering 114 A at the top of the operating range. The TM240 thermal-magnetic release handles overload and short-circuit protection without an electronic trip unit, keeping the design simple and field-replaceable. Breaking capacity is the headline number for this class: 121 kA at 240 V AC, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at both 500 V and 690 V. The 121 kA figure at 240 V means it can safely interrupt a fault current up to that level without cascading upstream — critical for high-fault panels near large transformers or service entrances. Rated insulation voltage is 800 V, so it handles 480 V and 600 V class systems with headroom. The breaker ships with one auxiliary switch and one trip alarm switch (HQ configuration) factory-installed, giving a dry-contact status signal for PLC or annunciator inputs. A mechanical trip indicator is present on the front face — no undervoltage release, no ground-fault monitoring, no communication module. This is a straightforward line-protection MCCB, not a multifunction power breaker.

Mounting and panel fit

Dimensions are 130 mm height, 76.2 mm width, 70 mm depth. The 70 mm depth is shallow enough for most 200 mm deep enclosures without crowding the gland plate. Width at 76.2 mm is standard for a 3-pole MCCB in this frame size — it occupies three 25 mm module spaces on a DIN rail or bolts directly to a mounting plate via the rear slots. The 3VA1 family uses a common footprint across current ratings, so swapping a 100 A unit for this 125 A unit does not require re-drilling the backplate.

Thermal performance across the panel ambient range

Rated current holds flat at 125 A from 40 °C through 50 °C. At 55 °C it drops to 122 A, at 60 °C to 120 A, at 65 °C to 117 A, and at 70 °C to 114 A. The derating curve is gentle — about 0.2 A per °C above 50 °C — so a panel running at 60 °C ambient still gets 96% of the nameplate rating. Maximum power loss at full load is 28.1 W, which is manageable for natural convection in a ventilated enclosure.

Environmental limits

Operating temperature range is -25 °C to +70 °C. Storage range extends from -40 °C to +80 °C — the storage limit governs handling and warehousing, not running conditions. The -40 °C storage floor means it can sit in an unheated warehouse through winter without damage.

Frequently asked questions

Where can I buy 3VA1112-4EF36-0AF0 and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time, not a published figure.

What is 3VA1112-4EF36-0AF0's listed depth (70 mm) on this component line?

The listed depth is 70 mm (2.76 in). This is the body depth excluding any protruding handle or terminal covers.

What is 3VA1112-4EF36-0AF0's listed width (76.2 mm) on this component line?

The listed width is 76.2 mm (3 in), standard for a 3-pole MCCB in this frame size.

Will 3VA1112-4EF36-0AF0 drop into a panel that was specified around 3VA1112-5EE32-0AA0 without rewiring?

Mechanically yes — both are 3-pole SENTRON 3VA1 breakers with identical mounting footprint (130 x 76.2 x 70 mm). The bus bar and lug positions are the same. Electrically, the trip unit differs: the 4EF36 uses a TM240 thermal-magnetic release, while the 5EE32 uses a different release. Verify the trip curve and SCCR coordination before swapping; the wiring itself does not need to change.

What compliance documentation does this brand provide for 3VA1112-4EF36-0AF0 (RoHS, REACH, UL, IEC)?

As a Siemens SENTRON product, this MCCB is designed to meet IEC 60947-2 and UL 489 standards. RoHS and REACH compliance declarations are available from Siemens on request. The evidence does not list specific certification marks, but the 3VA1 series is typically UL listed and CE marked for the European market.

MPN