It carries a continuous current of 125 A through 40 °C ambient, derating to 114 A at 70 °C. Breaking capacity is 121 kA at 240 V AC, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at both 500 V and 690 V.
Maximum power loss is 30.6 W. That matters for thermal management inside a sealed enclosure — account for that dissipation when sizing ventilation or calculating internal temperature rise.