Skip to main content
Siemens 3VA1112-4EF36-0JA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1112-4EF36-0JA0 SENTRON MCCB, 125 A, 3-Pole, 121

MPN3VA1112-4EF36-0JA0

Siemens SENTRON 3VA1112-4EF36-0JA0, molded case circuit breaker, 3-pole, 125 A, TM240 thermal-magnetic release, 121 kA at 240 V, 70 mm depth.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1112-4EF36-0JA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA1112-4EF36-0JA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C125 A
Current at 45 °C125 A
Current at 50 °C125 A
Current at 55 °C120 A
Current at 60 °C117.5 A
Current at 65 °C115 A
Current at 70 °C112.5 A
Switching capacity classS
Breaking capacity at 240 V121 kA
Breaking capacity at 415 V75.6 kA
Breaking capacity at 440 V52.5 kA
Breaking capacity at 690 V11.9 kA

Protection & Trip Unit

3VA1112-4EF36-0JA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240

Construction & Connection

3VA1112-4EF36-0JA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1112-4EF36-0JA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1112-4EF36-0JA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1112-4EF36-0JA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

What this MCCB carries — and what that means for your panel

The Siemens 3VA1112-4EF36-0JA0 is a 3-pole SENTRON molded case circuit breaker rated for 125 A continuous current (Iu) with a TM240 thermal-magnetic release. The 125 A rating holds flat from 40 °C to 50 °C, then derates to 120 A at 55 °C, 117.5 A at 60 °C, 115 A at 65 °C, and 112.5 A at 70 °C — so if your panel ambient runs hot, you lose about 10 % of the headline number by the time you hit 70 °C. That derating curve is the spec that decides whether this breaker holds a full 125 A feeder or needs to be upsized for a warm enclosure. Interrupting capacity is 121 kA at 240 V, 75.6 kA at 415 V, 52.5 kA at 440 V, and 11.9 kA at 690 V. At 415 V — common in European industrial distribution — the 75.6 kA rating comfortably handles high-fault scenarios like transformer secondaries or large motor centers without needing a current-limiting upstream device.

Panel fit and integration

Dimensions: 70 mm depth, 76.2 mm width, 130 mm height. The 76.2 mm width fits Siemens SENTRON mounting plates and most DIN-rail adapters. Front protection is IP40 — sealed against tools and small wires, but not against washdown. Keep this behind a panel door in any wet or dusty environment.

Release and accessories — what's on board, what's not

The TM240 overcurrent release is a thermal-magnetic type — fixed thermal curve for overload, magnetic pickup for short-circuit. No electronic adjustment, no communication module, no phase-failure detection. The auxiliary release is a shunt trip (STL) — the integrated auxiliary trip order code is 3VA9688-0BL32, so if you need remote tripping capability, that's the add-on part number to specify alongside this breaker. No auxiliary contact version is included (without). No undervoltage release. No ground-fault monitoring. If your application demands any of those, you'll need a different variant or an external module.

Frequently asked questions

Will 3VA1112-4EF36-0JA0 drop into a panel that was specified around 3VA1112-5EF32-0CA0 without rewiring?

Both are 3-pole SENTRON MCCBs with the same physical footprint (70 mm depth, 76.2 mm width, 130 mm height), so they share the same mounting hole pattern and busbar spacing. The key difference is the overcurrent release: this one uses a TM240 thermal-magnetic release, while the 3VA1112-5EF32-0CA0 uses an electronic release. If the panel was wired for an electronic release with external current transformers or a communication bus, the TM240 version won't connect to those. For a straight line-protection swap without auxiliaries, it fits mechanically.

What is 3VA1112-4EF36-0JA0's listed depth (70 mm) on this component line?

The depth is 70 mm, as listed in the manufacturer specifications.

What is 3VA1112-4EF36-0JA0's listed width (76.2 mm) on this component line?

The width is 76.2 mm, as listed in the manufacturer specifications.

MPN