Siemens 3VA1112-5ED26-0AA0 SENTRON MCCB, 125A, 2-Pole, 187kA

MPN3VA1112-5ED26-0AA0
Active

Siemens SENTRON 3VA1112-5ED26-0AA0, molded case circuit breaker, 2-pole, TM210 thermal-magnetic release, 125 A at 40 °C, interrupting capacity 187 kA at 240 V AC, 121 kA at 415 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA1112-5ED26-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1112-5ED26-0AA0 — Ratings
ParameterValue
Number of poles2
Rated operational voltage Ue (AC)415 V
Current at 40 °C125 A
Current at 45 °C125 A
Current at 50 °C125 A
Current at 55 °C122 A
Current at 60 °C120 A
Current at 65 °C117 A
Current at 70 °C114 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Power loss, max.18.74 W
3VA1112-5ED26-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VA1112-5ED26-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1112-5ED26-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA1112-5ED26-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1112-5ED26-0AA0 — Mechanical
ParameterValue
Height130 mm
Width50.8 mm
Depth70 mm
Height (in)5.12 in
Width (in)2 in
Depth (in)2.76 in

Product details

Thermal derating — the real-world current rating

Above that, the TM210 release starts to pull back: 122 A at 55 °C, 120 A at 60 °C, 117 A at 65 °C, 114 A at 70 °C. The thermal curve is the binding limit, not the nameplate.

Dimensions are 70 mm deep, 50.8 mm wide, 130 mm tall — a standard 2-pole MCCB footprint for DIN-rail or screw-mount panel assembly. Front IP40 protection means it's splash-safe from the front but not sealed for washdown; keep it inside the enclosure.

Frequently asked questions

Where can I buy 3VA1112-5ED26-0AA0 and what is the price?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

Will 3VA1112-5ED26-0AA0 drop into a panel specified for 3VA1112-5EE32-0AA0 without rewiring?

Both are 2-pole SENTRON MCCBs with the same physical footprint (70 mm depth, 50.8 mm width, 130 mm height) and the same 125 A rating at 40 °C, so they share the same mounting and bus-bar pattern. The difference is the overcurrent release design — this one uses TM210; the 5EE32 variant uses a different release. Check the release curve against your coordination study before swapping.

What compliance documentation does Siemens provide for this MCCB?

The SENTRON 3VA series typically carries UL, CSA, IEC 60947-2, and CE marking. Specific documentation (RoHS, REACH, Declaration of Conformity) is available from Siemens upon request or through their support portal.