Skip to main content
Siemens 3VA1112-5ED32-0AH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1112-5ED32-0AH0 SENTRON MCCB, 125 A, 187 kA at 24

MPN3VA1112-5ED32-0AH0

Siemens SENTRON 3VA1112-5ED32-0AH0, 3-pole molded case circuit breaker, 125 A rated continuous current, TM210 thermal-magnetic release, 187 kA breaking capacity at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1112-5ED32-0AH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1112-5ED32-0AH0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C125 A
Current at 45 °C125 A
Current at 50 °C125 A
Current at 55 °C120 A
Current at 60 °C117.5 A
Current at 65 °C115 A
Current at 70 °C112.5 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 690 V17 kA
3VA1112-5ED32-0AH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1112-5ED32-0AH0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1112-5ED32-0AH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1112-5ED32-0AH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1112-5ED32-0AH0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens 3VA1112-5ED32-0AH0 is a 3-pole SENTRON molded case circuit breaker rated for 125 A continuous current (Iu) across ambient temperatures up to 50 °C, with a slight derating curve beginning at 55 °C down to 112.5 A at 70 °C. The TM210 thermal-magnetic release handles the overcurrent and short-circuit protection without an undervoltage or ground-fault module — it's a straight line-protection device meant for distribution panels and feeder circuits. At 240 V it interrupts 187 kA; at 415 V, 121 kA; at 440 V, 75.6 kA; at 690 V, 17 kA. That spread tells you the arc extinction is voltage-dependent — the 690 V figure is still respectable for a 125 A frame, but the real strength is in the 400–480 V class where most industrial distribution lives.

Footprint is 130 mm tall, 76.2 mm wide, 70 mm deep — a standard 3-pole MCCB envelope that drops into SENTRON mounting plates and DIN-rail adapters without surprises. That's enough to send a remote status and a separate fault signal back to the PLC or annunciator without adding a module later.

Frequently asked questions

What is the breaking capacity of this MCCB at 415 V?

121 kA at 415 V, which is the typical three-phase distribution voltage in many industrial plants.

Where can I buy the Siemens 3VA1112-5ED32-0AH0?

This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

Does the 3VA1112-5ED32-0AH0 include auxiliary contacts?

Yes, it comes with 2 auxiliary switches plus 1 trip alarm switch (HQ type) factory-installed.

What overcurrent release does this breaker use?

The TM210 thermal-magnetic release, which provides both overload (thermal) and short-circuit (magnetic) protection without electronic adjustments.

MPN
3VA1112-5ED32-0AH0