Skip to main content
Siemens 3VA1112-5ED32-0BH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1112-5ED32-0BH0 SENTRON MCCB, 125 A, 187 kA at 24

MPN3VA1112-5ED32-0BH0

Siemens SENTRON 3VA1112-5ED32-0BH0, 3-pole molded case circuit breaker, 125 A (40 °C), 187 kA at 240 VAC, line protection, with undervoltage release and auxiliary switches.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1112-5ED32-0BH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11125ED320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1112-5ED32-0BH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C125 A
Current at 45 °C125 A
Current at 50 °C125 A
Current at 55 °C122 A
Current at 60 °C120 A
Current at 65 °C117 A
Current at 70 °C114 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.30.6 W
3VA1112-5ED32-0BH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1112-5ED32-0BH0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1112-5ED32-0BH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1112-5ED32-0BH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1112-5ED32-0BH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The Siemens 3VA1112-5ED32-0BH0 is a SENTRON 3-pole molded case circuit breaker (MCCB) for line protection, rated 125 A at 40 °C and carrying a 187 kA interrupting capacity at 240 VAC — enough to handle high-fault utility feeds or transformer secondaries without cascading upstream breakers. At 415 V it still breaks 121 kA, and at 690 V it holds 17 kA, so the same frame covers both 400 V and 690 V distribution without a derate on the interrupting rating. The thermal derating curve is published: 125 A continuous up to 50 °C, then 122 A at 55 °C, 120 A at 60 °C, 117 A at 65 °C, and 114 A at 70 °C — useful when the breaker sits in a crowded, warm panel.

The UVR drops the breaker on loss of control voltage — standard for safety circuits where a downstream contactor or safety relay must not re-energise until the supply is stable.

The 3VA1112-5ED32-0BH0 measures 130 mm high, 76.2 mm wide, and 70 mm deep — a standard 3-pole MCCB footprint that mounts on DIN rail or panel-mount adapter.

Frequently asked questions

What auxiliary switches does this MCCB include?

It includes 2 auxiliary switches plus 1 trip alarm switch (HQ type), and an undervoltage release.

MPN