Skip to main content
Siemens 3VA1112-5ED32-0DC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1112-5ED32-0DC0 SENTRON MCCB, 125 A, 187 kA at 24

MPN3VA1112-5ED32-0DC0

Siemens SENTRON 3VA1112-5ED32-0DC0, molded case circuit breaker, 3-pole, line protection, 125 A rated continuous current, TM210 thermal-magnetic release, 187 kA breaking capacity at 240 V, undervoltage release, 2 HQ auxiliary switches, IP40 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1112-5ED32-0DC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1112-5ED32-0DC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C125 A
Current at 45 °C125 A
Current at 50 °C125 A
Current at 55 °C120 A
Current at 60 °C117.5 A
Current at 65 °C115 A
Current at 70 °C112.5 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 690 V17 kA
3VA1112-5ED32-0DC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1112-5ED32-0DC0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1112-5ED32-0DC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1112-5ED32-0DC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1112-5ED32-0DC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens SENTRON 3VA1112-5ED32-0DC0 is a 3-pole molded case circuit breaker (MCCB) rated for line protection, carrying 125 A continuous current at 40 °C through 50 °C without derating. That 125 A holds flat across the first three temperature steps — at 55 °C it drops to 120 A, at 60 °C to 117.5 A, at 65 °C to 115 A, and at 70 °C to 112.5 A. Breaking capacity is the headline number here: 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 690 V. The 690 V figure of 17 kA is lower but still covers most motor-circuit fault levels at that voltage. Keep it simple.

For a BOM line that needs this exact configuration — 125 A, TM210 release, UVR, 2 aux switches — the 3VA1112-5ED32-0DC0 is the correct order code. If your panel was specified around the sibling 3VA1112-5EF32-0CA0, the difference is in the release type (EF vs ED); verify the release curve matches your coordination study before substituting. The mechanical footprint — 70 mm depth, 76.2 mm width, 130 mm height — is identical across the 3VA1112 frame, so panel cutouts and busbar positions are the same.

Mounts in a standard distribution panel via the SENTRON 3VA base plate or DIN rail adapter (not included). The 76.2 mm width is a 4-module footprint at 19.05 mm per module — common for Siemens switchgear. That UVR is the 3VA9608-0BB25 auxiliary trip unit, field-replaceable if it fails. Two HQ (high-quality) auxiliary switches are built in, providing status feedback for the open/closed position. No communication function, no phase failure detection, no voltage trigger — this is a pure protection device with basic signaling.

Frequently asked questions

How do I get current pricing and availability for 3VA1112-5ED32-0DC0?

Submit an RFQ through this listing. Pricing and stock are confirmed at quote time through our independent distribution network — we source across multiple channels to cover configured variants like this one.

Will 3VA1112-5ED32-0DC0 drop into a panel specified around 3VA1112-5EF32-0CA0 without rewiring?

The mechanical footprint is identical — 70 mm depth, 76.2 mm width, 130 mm height — so the panel cutout and busbar positions are the same. The difference is in the overcurrent release type (TM210 on this unit versus the EF release on the sibling). Verify the release curve matches your coordination study before substituting.

What are the key ratings of 3VA1112-5ED32-0DC0?

Rated continuous current 125 A (derated above 50 °C), breaking capacity 187 kA at 240 V / 121 kA at 415 V / 75.6 kA at 440 V / 17 kA at 690 V, rated insulation voltage 800 V, 3-pole, TM210 thermal-magnetic release, undervoltage release included, 2 HQ auxiliary switches, IP40 front protection.

MPN
3VA1112-5ED32-0DC0