Siemens SENTRON 3VA1112-5ED32-0HA0 — 125 A MCCB with TM210 Release and Shunt Trip
It carries an insulation voltage Ui of 800 V, and its breaking capacity is specified across four voltage levels: 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 690 V — the figure at 415 V is the one most often used for selectivity studies in 400 V distribution.
Thermal Derating and Temperature Range
Above that, it derates stepwise: 120 A at 55 °C, 117.5 A at 60 °C, 115 A at 65 °C, and 112.5 A at 70 °C.
Mechanical Endurance and Dimensions
Physical footprint: 130 mm height, 76.2 mm width (roughly 3 inches — fits standard 3-pole MCCB panel cutouts), 70 mm depth.