Skip to main content
Siemens 3VA1112-5ED32-0JC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1112-5ED32-0JC0 SENTRON MCCB, 125 A, 3-Pole, Line

MPN3VA1112-5ED32-0JC0

Siemens SENTRON 3VA1112-5ED32-0JC0, 3-pole molded case circuit breaker, 125 A rated continuous current, TM210 thermal-magnetic release, line protection version, breaking capacity 187 kA at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1112-5ED32-0JC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1112-5ED32-0JC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C125 A
Current at 45 °C125 A
Current at 50 °C125 A
Current at 55 °C120 A
Current at 60 °C117.5 A
Current at 65 °C115 A
Current at 70 °C112.5 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 690 V17 kA
3VA1112-5ED32-0JC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1112-5ED32-0JC0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1112-5ED32-0JC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1112-5ED32-0JC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1112-5ED32-0JC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

125 A MCCB for Feeder and Distribution Protection

The TM210 thermal-magnetic release provides fixed overload and short-circuit protection curves suited to feeder circuits, not adjustable electronic trip units — a deliberate choice when simplicity and reliability outweigh coordination flexibility. Breaking capacity reaches 187 kA at 240 V AC, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 690 V, so it handles high-fault utility feeds without cascading upstream.

Full 125 A rating holds through 50 °C ambient; above that, the breaker derates linearly to 120 A at 55 °C, 117.5 A at 60 °C, 115 A at 65 °C, and 112.5 A at 70 °C.

Integrated Auxiliary and Shunt Trip

The integrated auxiliary trip accessory carries order code 3VA9688-0BL32 — a factory-fitted component, not a field-add kit. The shunt trip allows a PLC or emergency-stop circuit to open the breaker remotely, critical for safety circuits or unattended machinery.

Frequently asked questions

Where can I buy 3VA1112-5ED32-0JC0?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of 3VA1112-5ED32-0JC0 at different voltages?

Breaking capacity is 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 690 V AC.

What is the difference between 3VA1112-5ED32-0JC0 and 3VA1112-5EF32-0CA0?

The 3VA1112-5EF32-0CA0 carries a different release or accessory configuration — the 5ED32 variant here includes a shunt trip and two auxiliary switches. Panel footprint (3-pole, same frame) is identical, so mechanical fit is the same, but the internal trip and auxiliary wiring differ. Verify the BOM release code before substituting.

MPN
3VA1112-5ED32-0JC0