The Siemens 3VA1112-5ED32-0KA0 is a SENTRON 3-pole molded case circuit breaker (MCCB) rated for line protection, carrying a continuous current Iu of 125 A at 40 °C and an insulation voltage Ui of 800 V. Its interrupting capacity hits 187 kA at 240 V, 121 kA at 415 V, and 75.6 kA at 440 V — numbers that matter when coordinating downstream faults without cascading upstream.
The 125 A continuous rating holds steady up to 50 °C; above that it derates to 117.5 A at 60 °C and 112.5 A at 70 °C — check your enclosure ambient before sizing.