Skip to main content
Siemens 3VA1112-5ED42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1112-5ED42-0AA0 SENTRON MCCB, 125 A, 4-Pole, 187

MPN3VA1112-5ED42-0AA0
Active

Siemens SENTRON 3VA1112-5ED42-0AA0, 4-pole molded case circuit breaker, 125 A (40 °C), TM210 thermal-magnetic release, 187 kA at 240 V, 121 kA at 415 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1112-5ED42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1112-5ED42-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Current at 40 °C125 A
Current at 45 °C125 A
Current at 50 °C125 A
Current at 55 °C122 A
Current at 60 °C120 A
Current at 65 °C117 A
Current at 70 °C114 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.28.1 W
3VA1112-5ED42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VA1112-5ED42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1112-5ED42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1112-5ED42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1112-5ED42-0AA0 — Mechanical
ParameterValue
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

At 440 V AC the breaker still clears 75.6 kA, and at 500 V and 690 V it holds 17 kA. That spread means it can serve as a main breaker on a 480 V panel or a feeder breaker in a 690 V industrial system, though at higher voltages the available fault current must stay under 17 kA.

The 3VA1112-5ED42-0AA0 measures 101.6 mm wide, 130 mm tall, and 70 mm deep — a compact 4-pole footprint that fits standard distribution panelboards. Maximum power loss is 28.1 W, which matters for thermal budgeting in a sealed enclosure.

Frequently asked questions

How do I get current pricing and availability for 3VA1112-5ED42-0AA0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commitment.

Will 3VA1112-5ED42-0AA0 drop into a panel specified around 3VA1112-5EE32-0AA0 without rewiring?

Both are 4-pole SENTRON 3VA1 MCCBs sharing the same 101.6 mm width and 70 mm depth, so the mechanical footprint is identical. The deciding difference is the overcurrent release: the 5ED42-0AA0 uses a TM210 thermal-magnetic release, while the 5EE32-0AA0 uses a different release variant. Verify the trip curve and rating match your coordination study before swapping.

What compliance documentation does this brand provide for 3VA1112-5ED42-0AA0?

As a Siemens SENTRON product, the 3VA1112-5ED42-0AA0 carries standard IEC/EN 60947-2 certification for molded case circuit breakers. Compliance documentation including RoHS and REACH declarations is available through Siemens Industry Online Support. The rated insulation voltage is 800 V.

MPN
3VA1112-5ED42-0AA0