Skip to main content
Siemens 3VA1112-5EF32-0HC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1112-5EF32-0HC0 MCCB, 125 A, 3-Pole, 187 kA at 24

MPN3VA1112-5EF32-0HC0

Siemens SENTRON 3VA1112-5EF32-0HC0, molded case circuit breaker, 3-pole, 125 A (40 °C), 187 kA at 240 V, line protection, with shunt trip (STL) and 2 HQ auxiliary switches.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1112-5EF32-0HC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11125EF320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA1112-5EF32-0HC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C125 A
Current at 45 °C125 A
Current at 50 °C125 A
Current at 55 °C122 A
Current at 60 °C120 A
Current at 65 °C117 A
Current at 70 °C114 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.28.1 W

Protection & Trip Unit

3VA1112-5EF32-0HC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1112-5EF32-0HC0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1112-5EF32-0HC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1112-5EF32-0HC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1112-5EF32-0HC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

Line protection MCCB with shunt trip and auxiliary switches

The Siemens SENTRON 3VA1112-5EF32-0HC0 is a 3-pole molded case circuit breaker rated 125 A at 40 °C, designed for line protection in distribution panels. It carries a 187 kA interrupting capacity at 240 V — enough headroom for high-fault service-entrance or subdistribution applications where the available fault current is substantial. The breaker includes a factory-fitted shunt trip (STL) for remote tripping and two HQ auxiliary switches for status feedback to a PLC or annunciator panel.

Interrupting ratings across voltage bands

This MCCB delivers 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at both 500 V and 690 V. The steep drop above 440 V is typical of a high-breaking-capacity frame — at 690 V the 17 kA still covers most industrial motor branch circuits, but for a 690 V main you would want to verify the downstream coordination study.

Current derating with ambient temperature

The breaker holds 125 A continuously from 40 °C up to 50 °C, then derates to 122 A at 55 °C, 120 A at 60 °C, 117 A at 65 °C, and 114 A at 70 °C. If the panel ambient runs above 50 °C — common in a non-ventilated enclosure near a furnace or kiln — the 114 A floor at 70 °C still leaves margin for a 100 A continuous load, but a 125 A load would need the next frame up or forced ventilation.

Panel fit and integration

Dimensions are 130 mm height, 76.2 mm width, and 70 mm depth. The 3-pole width (about 3 in) fits standard MCCB mounting feet on a DIN rail or panel-mount base. The shunt trip coil and auxiliary switches are pre-wired to terminal blocks; no additional wiring of internal accessories is needed.

Frequently asked questions

Where can I buy 3VA1112-5EF32-0HC0?

The part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

Will 3VA1112-5EF32-0HC0 drop into a panel that was specified around 3VA1112-5EE32-0AA0 without rewiring?

Both are 3-pole SENTRON MCCBs with the same frame dimensions (130 mm height, 76.2 mm width, 70 mm depth) and the same 125 A rating at 40 °C. The -0HC0 variant adds a shunt trip and two HQ auxiliary switches, so the physical fit and bus connections are identical — no rewiring of the main power path is needed. The additional control wiring for the shunt trip and aux switches would need to be run if the original panel did not already provide it.

MPN
3VA1112-5EF32-0HC0