Specifications

Identification

3VA1112-5EF36-0DH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11125EF360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12

Ratings

3VA1112-5EF36-0DH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C125 A
Current at 45 °C125 A
Current at 50 °C125 A
Current at 55 °C122 A
Current at 60 °C120 A
Current at 65 °C117 A
Current at 70 °C114 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.30.6 W

Protection & Trip Unit

3VA1112-5EF36-0DH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1112-5EF36-0DH0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1112-5EF36-0DH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3

Environmental

3VA1112-5EF36-0DH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1112-5EF36-0DH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

Siemens 3VA1112-5EF36-0DH0 — 125 A SENTRON MCCB with Undervoltage Release

The Siemens 3VA1112-5EF36-0DH0 is a SENTRON molded case circuit breaker (MCCB) rated for 125 A continuous at 40 °C, 3-pole, designed for line protection in distribution and motor control center applications. Its interrupting capacity reaches 187 kA at 240 V AC, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at 500 V and 690 V — figures that govern selectivity and fault-clearing capability in high-fault industrial networks. The breaker carries a rated insulation voltage of 800 V and includes an undervoltage release (UVR) as the auxiliary release, plus a factory-fitted auxiliary switch block with 2 auxiliary switches and 1 trip alarm switch (HQ). Maximum power loss is 30.6 W at rated current.

Thermal Derating and Ambient Operating Range

The 125 A rating holds from 40 °C through 50 °C ambient. Above that, derating is linear: 122 A at 55 °C, 120 A at 60 °C, 117 A at 65 °C, and 114 A at 70 °C. The operating ambient range is -25 °C to +70 °C, with storage from -40 °C to +80 °C. For a panel running warm — say, 55 °C inside the enclosure — the usable current is 122 A, not the full 125 A. That 3 A difference matters when sizing for a continuous load near the breaker's nameplate.

Physical Integration and Auxiliary Wiring

Dimensions are 130 mm height, 76.2 mm width, 70 mm depth — a 3-pole MCCB footprint that fits standard SENTRON panel cutouts and busbar systems. The auxiliary switch block (2 aux + 1 trip alarm HQ) and the undervoltage release are pre-configured at the factory; no field assembly of internal accessories is required. The UVR coil wiring must be routed to a separate control voltage source — it is not self-powered from the breaker's line side.

Frequently asked questions

What are the interrupting ratings for this MCCB?

At 240 V AC: 187 kA. At 415 V: 121 kA. At 440 V: 75.6 kA. At 500 V and 690 V: 17 kA. These are the maximum fault currents the breaker can safely interrupt at each voltage level.