Skip to main content
Siemens 3VA1112-5EF36-0HC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1112-5EF36-0HC0 SENTRON MCCB, 125 A, 3-Pole, 187

MPN3VA1112-5EF36-0HC0

Siemens SENTRON 3VA1112-5EF36-0HC0, molded case circuit breaker, 3-pole, 125 A rated current at 40-50 °C, 187 kA breaking capacity at 240 V, line protection design, with shunt trip release.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1112-5EF36-0HC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11125EF360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12

Ratings

3VA1112-5EF36-0HC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C125 A
Current at 45 °C125 A
Current at 50 °C125 A
Current at 55 °C122 A
Current at 60 °C120 A
Current at 65 °C117 A
Current at 70 °C114 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.28.1 W

Protection & Trip Unit

3VA1112-5EF36-0HC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo

Construction & Connection

3VA1112-5EF36-0HC0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1112-5EF36-0HC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2

Environmental

3VA1112-5EF36-0HC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1112-5EF36-0HC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The Siemens SENTRON 3VA1112-5EF36-0HC0 is a 3-pole molded case circuit breaker (MCCB) rated for 125 A continuous current across the 40-50 °C ambient range, with a full-rated 125 A up to 50 °C before derating begins at 55 °C. Breaking capacity hits 187 kA at 240 V AC, stepping down to 121 kA at 415 V and 75.6 kA at 440 V — numbers that cover most industrial distribution panels and motor control center feeder applications. The 70 mm depth and 76.2 mm width fit standard Siemens 3VA panel footprints, so it drops into existing SENTRON busbar systems without re-drilling.

Ratings and what they mean for your panel

The 125 A rating at 40-50 °C is the thermal-magnetic trip baseline — this breaker carries that current continuously without nuisance tripping in a typical 40 °C panel environment. Above 50 °C, derating is gradual: 122 A at 55 °C, 120 A at 60 °C, 117 A at 65 °C, and 114 A at 70 °C. If your enclosure runs hot, factor those numbers into the load calculation rather than oversizing the frame. The 187 kA interrupting rating at 240 V is the headline number for high-fault locations — think service entrance or large transformer secondary. At 415 V (common in European industrial grids) it still clears 121 kA, and at 440 V it handles 75.6 kA. Those are SCCR values, not withstand ratings; the breaker must open on fault, not just pass current through.

Built-in release and switching configuration

This variant ships with a shunt trip release (STL) for remote tripping — useful for emergency-stop circuits or supervisory control systems that need to drop the breaker from a PLC or safety relay. The auxiliary switch block carries 2 HQ (high-availability) contacts for status feedback to the control system. There is no undervoltage release on this order code, so if you need UVR for undervoltage protection, you will want a different suffix. The breaker is designed for line protection (cable and busbar protection), not motor protection — no thermal overload curve matched to motor start-up. For motor branch circuits, pair it with a separate overload relay upstream or downstream.

Physical fit and panel integration

Dimensions: 130 mm height, 76.2 mm width (3 inches), 70 mm depth (2.76 inches). The 3-pole width matches the standard 3VA1112 frame — it occupies one 76.2 mm slot on the SENTRON busbar system. Depth of 70 mm leaves room for rear-connected busbars or cable lugs in a standard 200 mm deep enclosure. Mounts on DIN rail or direct panel mount via the 3VA base. The 70 mm depth is the overall body dimension including the rotary handle; no extra projection for the shunt trip module since it is integrated inside the frame.

Frequently asked questions

What is the breaking capacity of this MCCB at different voltages?

187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at both 500 V and 690 V.

Does the 3VA1112-5EF36-0HC0 include a shunt trip?

Yes, it ships with a shunt trip release (STL) for remote tripping, plus 2 HQ auxiliary switches for status feedback.

Where can I buy the 3VA1112-5EF36-0HC0?

Sourced and quoted to order against an RFQ through independent distribution. Submit a request for current pricing and availability.

MPN
3VA1112-5EF36-0HC0