Skip to main content
Siemens 3VA1112-5GD42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1112-5GD42-0AA0 SENTRON MCCB, 125 A, 4-Pole, TM21

MPN3VA1112-5GD42-0AA0
Active

Siemens SENTRON 3VA1112-5GD42-0AA0, molded case circuit breaker, 4-pole, 125 A, TM210 overcurrent release, line protection design.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1112-5GD42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA1112-5GD42-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C125 A
Current at 45 °C125 A
Current at 50 °C125 A
Current at 55 °C122 A
Current at 60 °C120 A
Current at 65 °C117 A
Current at 70 °C114 A
Switching capacity classM
Breaking capacity at 240 V187 kA
Breaking capacity at 415 V121 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.28.1 W
3VA1112-5GD42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1112-5GD42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1112-5GD42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1112-5GD42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1112-5GD42-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

125 A, 4-pole MCCB with TM210 release — still in current production

The 3VA1112-5GD42-0AA0: Breaking capacity is rated per IEC 60947-2: 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at both 500 V and 690 V. That gives you substantial SCCR headroom for high-fault installations — selectivity coordination with upstream gear is straightforward at these levels.

Dimensions: 130 mm height, 101.6 mm width, 70 mm depth. Four-pole width at 101.6 mm matches the standard 4-module MCCB footprint on DIN rail or bolted bus. Operating temperature range is -25 °C to +70 °C, with a derating curve starting at 55 °C: 122 A at 55 °C, 120 A at 60 °C, 117 A at 65 °C, 114 A at 70 °C. That covers most industrial environments including unheated electrical rooms and outdoor enclosures in temperate climates. No IP rating on the sides or rear; the breaker relies on the enclosure for overall ingress protection.

For BOM freeze or compliance documentation, the SENTRON 3VA series carries IEC 60947-2 certification. RoHS and REACH declarations are standard from Siemens for this product family.

Frequently asked questions

Where can I buy 3VA1112-5GD42-0AA0 and what is the lead time?

This part is sourced to order through independent distribution. Submit an RFQ for current availability and lead time — pricing and stock are confirmed at quote time.

What is 3VA1112-5GD42-0AA0's breaking capacity at different voltages?

Rated breaking capacity per IEC 60947-2: 187 kA at 240 V, 121 kA at 415 V, 75.6 kA at 440 V, and 17 kA at both 500 V and 690 V.

Will 3VA1112-5GD42-0AA0 drop into a panel specified around 3VA1112-5EE32-0AA0?

Both are 4-pole SENTRON 3VA breakers with the same 101.6 mm width and 70 mm depth, so the mechanical footprint is identical. The key difference is the overcurrent release: this unit has a TM210, while the 3VA1112-5EE32-0AA0 carries a different release type. Verify the trip curve matches your coordination study before substituting.

MPN
3VA1112-5GD42-0AA0