Skip to main content
Siemens 3VA1112-5GF42-0AA0-ZD00 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1112-5GF42-0AA0-ZD00 3VA1 IEC Frame 160, 55kA @ 4

MPN3VA1112-5GF42-0AA0-ZD00

Siemens SENTRON 3VA1 IEC frame 160, breaking capacity class M, 4-pole, 125A, TM240 ATAM, line protection with N-conductor protection.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Product details

This 3VA1 Frame 160 Breaker

The Siemens 3VA1112-5GF42-0AA0-ZD00 is a 3VA1 IEC frame 160 molded-case circuit breaker, breaking capacity class M rated Icu=55kA @ 415V, 4-pole. It carries a TM240 thermal-magnetic trip unit with ATAM (adjustable thermal, adjustable magnetic) — overload protection Ir adjustable from 88A to 125A, short-circuit protection Ii adjustable 5...10 x In. N-conductor protection is set at 100%. Includes a nut keeper kit for DC Power OEM applications, specified for builds in China.

What the Ratings Mean for Fit

55 kA Icu at 415 V is the ultimate short-circuit breaking capacity — the breaker can safely interrupt a fault at that level once and still carry rated current afterward (no need to replace after a single fault). The class M designation sits between standard (S) and very high (H) in the 3VA line, giving you selectivity headroom for downstream distribution panels without overspending on the H frame. The 4-pole configuration with 100% N protection means the neutral conductor is switched and protected at the same rating as the phases — required for TN-C-S or TT systems where the neutral is a current-carrying conductor, not just a reference.

Panel Integration & Wiring

DIN-rail or screw-mount compatible within the 3VA1 frame footprint. The nut keeper kit (included) secures the DC Power OEM variant to the mounting plate — verify the gland plate clearance for the 4-pole width before laying out the enclosure. Spring-cage or box-lug terminals accept copper conductors sized for 125A continuous; torque per the terminal marking on the breaker face.

Frequently asked questions

Where can I buy 3VA1112-5GF42-0AA0-ZD00 and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for your volume.

What is the breaking capacity of this circuit breaker?

The 3VA1112-5GF42-0AA0-ZD00 has an Icu of 55 kA at 415 V, breaking capacity class M, on the 3VA1 IEC frame 160.

What is the adjustable trip range on this 125A breaker?

Overload protection Ir is adjustable from 88 A to 125 A via the TM240 ATAM trip unit. Short-circuit protection Ii adjusts from 5 to 10 times In (625 A to 1250 A). N-conductor protection is fixed at 100%.

MPN