Skip to main content
Siemens 3VA1112-6ED36-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1112-6ED36-0AA0 SENTRON MCCB, 125 A, 220 kA at 24

MPN3VA1112-6ED36-0AA0
Active

Siemens SENTRON 3VA1112-6ED36-0AA0, 3-pole molded case circuit breaker, 125 A continuous, TM210 thermal-magnetic release, 220 kA breaking capacity at 240 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1112-6ED36-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
3VA1112-6ED36-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C125 A
Current at 45 °C125 A
Current at 50 °C125 A
Current at 55 °C122 A
Current at 60 °C120 A
Current at 65 °C117 A
Current at 70 °C114 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.28.1 W
3VA1112-6ED36-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1112-6ED36-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1112-6ED36-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1112-6ED36-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1112-6ED36-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

At 70 mm deep × 76.2 mm wide × 130 mm tall, this breaker fits a standard MCCB footprint — 3 inches wide, which matches most panel-mount cutouts and bus-bar centers. Maximum power loss is 28.1 W at rated load — negligible for a single breaker, but factor it into a dense panel's heat budget if you are stacking several in a row.

Frequently asked questions

How do I get pricing and availability for 3VA1112-6ED36-0AA0?

We source and quote this breaker to order against an RFQ. Availability and current pricing are confirmed at quote time through independent distribution — no stock count or price figure is published here.

What is the depth of 3VA1112-6ED36-0AA0?

The depth is 70 mm (2.76 inches).

What is the width of 3VA1112-6ED36-0AA0?

The width is 76.2 mm (3 inches).

MPN
3VA1112-6ED36-0AA0