At 70 mm deep × 76.2 mm wide × 130 mm tall, this breaker fits a standard MCCB footprint — 3 inches wide, which matches most panel-mount cutouts and bus-bar centers. Maximum power loss is 28.1 W at rated load — negligible for a single breaker, but factor it into a dense panel's heat budget if you are stacking several in a row.

Siemens 3VA1112-6ED36-0AA0 SENTRON MCCB, 125 A, 220 kA at 24
MPN3VA1112-6ED36-0AA0
Active
Siemens SENTRON 3VA1112-6ED36-0AA0, 3-pole molded case circuit breaker, 125 A continuous, TM210 thermal-magnetic release, 220 kA breaking capacity at 240 V AC.
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026
Specifications
| Parameter | Value |
|---|---|
| Product designation | Molded case circuit breaker |
| Brand / range | SENTRON |
| Parameter | Value |
|---|---|
| Number of poles | 3 |
| Rated operational voltage Ue (AC) | 690 V |
| Rated insulation voltage Ui | 800 V |
| Current at 40 °C | 125 A |
| Current at 45 °C | 125 A |
| Current at 50 °C | 125 A |
| Current at 55 °C | 122 A |
| Current at 60 °C | 120 A |
| Current at 65 °C | 117 A |
| Current at 70 °C | 114 A |
| Switching capacity class | H |
| Breaking capacity at 240 V | 220 kA |
| Breaking capacity at 415 V | 154 kA |
| Breaking capacity at 440 V | 75.6 kA |
| Breaking capacity at 500 V | 17 kA |
| Breaking capacity at 690 V | 17 kA |
| Power loss, max. | 28.1 W |
| Parameter | Value |
|---|---|
| Overcurrent release (trip unit) type | TM210 |
| Overcurrent protection function | LI |
| Ground-fault monitoring | Without |
| Grounding protection function | No |
| Parameter | Value |
|---|---|
| Main circuit connection type | box terminal on both sides |
| Main circuit connector arrangement | Front terminal |
| Protection class (IP), front | IP40 |
| Parameter | Value |
|---|---|
| Undervoltage release | No |
| Voltage trigger | No |
| Trip indicator | No |
| Communication function | No |
| Measurement function | No |
| Motor drive option | Yes |
| Auxiliary CO contacts | 0 |
| Parameter | Value |
|---|---|
| Operating temperature, max. | 70 °C |
| Operating temperature, min. | -25 °C |
| Storage temperature, max. | 80 °C |
| Storage temperature, min. | -40 °C |
| Parameter | Value |
|---|---|
| Mechanical service life (operating cycles), typ. | 20 000 |
| Height | 130 mm |
| Width | 76.2 mm |
| Depth | 70 mm |
| Height (in) | 5.12 in |
| Width (in) | 3 in |
| Depth (in) | 2.76 in |
Product details
Frequently asked questions
How do I get pricing and availability for 3VA1112-6ED36-0AA0?
We source and quote this breaker to order against an RFQ. Availability and current pricing are confirmed at quote time through independent distribution — no stock count or price figure is published here.
What is the depth of 3VA1112-6ED36-0AA0?
The depth is 70 mm (2.76 inches).
What is the width of 3VA1112-6ED36-0AA0?
The width is 76.2 mm (3 inches).
MPN
3VA1112-6ED36-0AA0