Skip to main content
Siemens 3VA1112-6EF32-0AD0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1112-6EF32-0AD0 SENTRON MCCB, 125 A, 220 kA at 24

MPN3VA1112-6EF32-0AD0

Siemens SENTRON 3VA1112-6EF32-0AD0, 3-pole molded case circuit breaker, 125 A rated continuous current, TM240 thermal-magnetic release, 220 kA breaking capacity at 240 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1112-6EF32-0AD0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1112-6EF32-0AD0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C125 A
Current at 45 °C125 A
Current at 50 °C125 A
Current at 55 °C120 A
Current at 60 °C117.5 A
Current at 65 °C115 A
Current at 70 °C112.5 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 690 V17 kA
3VA1112-6EF32-0AD0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
3VA1112-6EF32-0AD0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1112-6EF32-0AD0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1112-6EF32-0AD0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1112-6EF32-0AD0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The 125 A continuous rating (Iu) holds flat from 40 °C up to 50 °C, then derates gradually: 120 A at 55 °C, 117.5 A at 60 °C, 115 A at 65 °C, and 112.5 A at 70 °C. Breaking capacity is what decides whether this breaker survives a fault or welds shut. At 240 V it's rated 220 kA — enough for high-fault utility feeds. At 415 V it's 154 kA, at 440 V it's 75.6 kA, and at 690 V it's 17 kA.

Thermal-magnetic release and auxiliary contacts

The overcurrent release is a TM240 — a fixed thermal-magnetic trip unit sized for 125 A frame. It ships with three HQ auxiliary switches (form C) for remote status feedback, so you can wire the breaker into a PLC or annunciator without adding a separate switch block.

The breaker measures 130 mm high, 76.2 mm wide, 70 mm deep — a standard 3-pole MCCB footprint for DIN-rail or panel-mount installation. Front protection is IP40 (tools and fingers stay out), and the operating temperature range is -25 °C to 70 °C, with storage from -40 °C to 80 °C. No trip indicator on the front, so status comes from the auxiliary contacts or a visual check of the handle position.

Frequently asked questions

Where can I buy 3VA1112-6EF32-0AD0 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What does the 125 A rating mean at higher panel temperatures?

The 125 A continuous rating holds up to 50 °C ambient; above that it derates to 120 A at 55 °C, 117.5 A at 60 °C, 115 A at 65 °C, and 112.5 A at 70 °C — so in a warm panel you still get full current up to 50 °C.

MPN
3VA1112-6EF32-0AD0