3VA1112-6EF32-0DH0 — SENTRON 125 A MCCB, 220 kA IC at 240 V
At 415 V it still clears 154 kA, dropping to 75.6 kA at 440 V and 17 kA at 690 V. This is the line-protection variant — no voltage trip, no phase-failure detection, no communication module. Front protection is IP40 — splash-safe in the cabinet but not washdown-rated. The TM240 release holds full 125 A up to 50 °C, then derates to 120 A at 55 °C, 117.5 A at 60 °C, 115 A at 65 °C, and 112.5 A at 70 °C.
At 415 V (common in European industrial panels), 154 kA still covers most utility-transformer fault levels. If the BOM needs adjustable overloads or a higher amp frame, look at the 5EF or 5EE siblings in the same 3VA1112 envelope.