Siemens 3VA1112-6EF32-0HC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1112-6EF32-0HC0 SENTRON MCCB, 3-pole, 125 A, TM24

MPN3VA1112-6EF32-0HC0

Siemens SENTRON 3VA1112-6EF32-0HC0, molded case circuit breaker, 3-pole, 125 A, TM240 overcurrent release, line protection, 220 kA interrupting at 240 V.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1112-6EF32-0HC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA11126EF320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1112-6EF32-0HC0 — Ratings
ParameterValue
Number of poles3
Current at 45 °C125 A
Current at 50 °C125 A
Current at 55 °C122 A
Current at 60 °C120 A
Current at 65 °C117 A
Current at 70 °C114 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.28.1 W
3VA1112-6EF32-0HC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VA1112-6EF32-0HC0 — Construction & Connection
ParameterValue
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1112-6EF32-0HC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerYes
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1112-6EF32-0HC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1112-6EF32-0HC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

It carries a rated insulation voltage Ui of 800 V and delivers interrupting ratings of 220 kA at 240 V, 154 kA at 415 V, 75.6 kA at 440 V, and 17 kA at both 500 V and 690 V — so it handles high-fault-current scenarios typical in industrial distribution panels without needing an upstream current-limiting fuse.

Thermal derating curve — the real ampacity

The 125 A rating holds at 45 °C and 50 °C, then derates: 122 A at 55 °C, 120 A at 60 °C, 117 A at 65 °C, and 114 A at 70 °C.

Auxiliary contacts and release options

This variant comes with 2 auxiliary switches (HQ type) for status feedback — useful for PLC inputs or remote indication. The voltage trigger is present, meaning it can accept a shunt trip or similar accessory.

Frequently asked questions

Who supplies 3VA1112-6EF32-0HC0 and how is it quoted for volume purchases?

This part is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time — no stock count or price is published here.

What are the interrupting ratings of 3VA1112-6EF32-0HC0 at different voltages?

220 kA at 240 V, 154 kA at 415 V, 75.6 kA at 440 V, and 17 kA at both 500 V and 690 V. That covers most industrial distribution voltages up to 690 V.

Will 3VA1112-6EF32-0HC0 drop into a panel that was specified around 3VA1110-5ED36-0AC0 without rewiring?

Both are 3-pole SENTRON MCCBs on the same 76.2 mm (3-inch) width footprint, so the panel cutout and bus-bar spacing should match. The key difference is the overcurrent release and interrupting rating — verify the trip curve and available fault current before swapping. No rewiring of the main bus is needed, but the auxiliary contact wiring may differ.

MPN
3VA1112-6EF32-0HC0