Skip to main content
Siemens 3VA1112-6GF42-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA1112-6GF42-0AA0 MCCB, 125 A, 4-Pole, 220

MPN3VA1112-6GF42-0AA0
Active

Siemens SENTRON 3VA1112-6GF42-0AA0, 4-pole molded case circuit breaker, 125 A rated current, TM240 thermal-magnetic release, 220 kA interrupting at 240 V AC.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

3VA1112-6GF42-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection

Ratings

3VA1112-6GF42-0AA0 — Ratings
ParameterValue
Number of poles4
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C125 A
Current at 45 °C125 A
Current at 50 °C125 A
Current at 55 °C122 A
Current at 60 °C120 A
Current at 65 °C117 A
Current at 70 °C114 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V17 kA
Breaking capacity at 690 V17 kA
Power loss, max.28.1 W

Protection & Trip Unit

3VA1112-6GF42-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM240
Overcurrent protection functionLI
Ground-fault monitoringWithout

Construction & Connection

3VA1112-6GF42-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40

Accessories & Functions

3VA1112-6GF42-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts0

Environmental

3VA1112-6GF42-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C

Mechanical

3VA1112-6GF42-0AA0 — Mechanical
ParameterValue
Height130 mm
Width101.6 mm
Depth70 mm
Height (in)5.12 in
Width (in)4 in
Depth (in)2.76 in

Product details

The 3VA1112-6GF42-0AA0: Compared to the 3VA1112-5EE32-0AA0 (also a 4-pole 125 A MCCB but with a different trip curve and lower interrupting ratings), this 6GF42 variant carries the higher SCCR — critical if your panel's available fault current exceeds 100 kA at 240 V. The physical footprint is identical: 101.6 mm wide, 130 mm tall, 70 mm deep. It drops into the same panel cutout and bus connection without rewiring, so a BOM substitution is straightforward as long as the trip curve matches the load.

Lifecycle status is current — no phase-out or NRND flags. That means the supply chain is stable; no last-time-buy clock ticking. For compliance, the SENTRON series carries UL 489, CSA C22.2 No. 5, and IEC 60947-2 certifications. RoHS and REACH declarations are standard from Siemens. If you need a formal declaration for your compliance file, it's available on request.

Mounts on a standard DIN rail or can be screw-mounted to a backplate. The front face carries an IP40 protection class — fine for a clean indoor panel, but not for washdown areas. The 4-pole design includes 100% rated neutral protection, so it's suited for three-phase plus neutral systems. The TM240 release is thermal-magnetic, adjustable for thermal pickup via a dial on the front. No undervoltage release or shunt trip fitted as standard — those are add-on accessories.

Frequently asked questions

Where can I buy 3VA1112-6GF42-0AA0 and how do I get a price?

This part is sourced to order through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time.

Will 3VA1112-6GF42-0AA0 drop into a panel specified around 3VA1112-5EE32-0AA0 without rewiring?

Yes, the dimensions are identical: 101.6 mm wide, 130 mm tall, 70 mm deep. The same mounting footprint and bus connections apply. Just confirm the trip curve matches your load.

What is the interrupting capacity of 3VA1112-6GF42-0AA0 at different voltages?

220 kA at 240 V AC, 154 kA at 415 V, 75.6 kA at 440 V, and 17 kA at both 500 V and 690 V.

MPN
3VA1112-6GF42-0AA0