Line protection breaker, 125 A, four poles
It carries a 220 kA interrupting capacity at 240 V, dropping to 154 kA at 415 V and 75.6 kA at 440 V — still substantial for most industrial distribution panels.
The 125 A rating holds up to 50 °C ambient; above that, derate to 122 A at 55 °C, 120 A at 60 °C, 117 A at 65 °C, and 114 A at 70 °C. The TM240 release has an adjustable li max of 1,250 A, giving you a 10× magnetic pickup window for motor-start inrush without nuisance trips. Mounting dimensions are 130 mm height, 101.6 mm width, 70 mm depth — fits standard SENTRON 3VA cutouts.