Skip to main content
Siemens 3VA1112-6MH32-0BC0 — Molded Case Circuit Breakers (MCCB)

3VA1112-6MH32-0BC0 SENTRON MCCB, 125A, 220kA at 240V

MPN3VA1112-6MH32-0BC0

Siemens SENTRON 3VA1112-6MH32-0BC0, molded case circuit breaker, 3-pole, 125 A rated, 220 kA breaking capacity at 240 V, undervoltage release, 2 auxiliary switches HQ.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1112-6MH32-0BC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11126MH320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1112-6MH32-0BC0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C125 A
Current at 45 °C125 A
Current at 50 °C125 A
Current at 55 °C122 A
Current at 60 °C120 A
Current at 65 °C117 A
Current at 70 °C114 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V7.5 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.30.6 W
3VA1112-6MH32-0BC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM120M
Overcurrent protection functionI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1112-6MH32-0BC0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1112-6MH32-0BC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1112-6MH32-0BC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1112-6MH32-0BC0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

The Siemens SENTRON 3VA1112-6MH32-0BC0 is a 3-pole molded case circuit breaker (MCCB) rated 125 A at 40 °C, with a breaking capacity of 220 kA at 240 V and 154 kA at 415 V — numbers that put it in the high-interrupting class for industrial distribution panels where fault currents can hit those levels.

Breaking capacity across voltages — what matters for selectivity

At 240 V this breaker clears 220 kA; at 415 V it's 154 kA; at 440 V it drops to 75.6 kA; and at 500 V and 690 V it holds at 7.5 kA. The steep drop above 440 V means you need to check the available fault current at the point of installation — if your system runs 480 V or 600 V class, the 7.5 kA rating may force a larger frame or a current-limiting fuse upstream.

Rated 125 A up to 50 °C; at 55 °C it's 122 A, at 60 °C it's 120 A, at 65 °C it's 117 A, and at 70 °C it's 114 A. The storage limit is wider because it's not under load — fine for warehousing spares. Maximum power loss is 30.6 W — that's the heat it dumps into the enclosure. If you're packing several of these in a small panel, add that to your thermal budget.

Bolts into a panel or mounts on a DIN rail adapter; the depth leaves room for rear-connected bus bars.