Skip to main content
Siemens 3VA1112-6MH36-0AF0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1112-6MH36-0AF0 SENTRON MCCB, 125 A, 220 kA at 24

MPN3VA1112-6MH36-0AF0

Siemens SENTRON 3VA1112-6MH36-0AF0, molded case circuit breaker, 3-pole, 125 A, TM120M thermal-magnetic release, 220 kA at 240 V, 1 aux + 1 trip alarm switch, IP40 front.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1112-6MH36-0AF0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionStarter protection
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1112-6MH36-0AF0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C125 A
Current at 45 °C125 A
Current at 50 °C125 A
Current at 55 °C122 A
Current at 60 °C120 A
Current at 65 °C117 A
Current at 70 °C114 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 690 V8.5 kA
3VA1112-6MH36-0AF0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM120M
3VA1112-6MH36-0AF0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1112-6MH36-0AF0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1112-6MH36-0AF0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1112-6MH36-0AF0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

Continuous current is 125 A at 40 °C, and it holds that rating all the way to 50 °C before it starts to derate: 122 A at 55 °C, 120 A at 60 °C, 117 A at 65 °C, and 114 A at 70 °C. That's a shallow derate curve, so you don't lose much capacity in a warm enclosure. Breaking capacity is the headline: 220 kA at 240 V, 154 kA at 415 V, 75.6 kA at 440 V, and 8.5 kA at 690 V. At 415 V — common for industrial three-phase — that 154 kA gives you serious fault-current headroom.

DIN-rail fit and panel integration

That's a standard SENTRON 3VA form factor — it clips onto the DIN rail and leaves room for side-by-side mounting with other 3VA breakers. The IP40 front rating means it's fine inside a closed panel; no washdown rating, so don't put it on the outside of a food-grade cabinet.

Starter-protection variant with TM120M release and auxiliary contacts. Footprint 130 × 76.2 × 70 mm matches 3VA1112 frame. Verify trip unit before replacing a 3VA1112-5EF32-0CA0.

Operating range and storage limits

Rated insulation voltage 800 V, max DC operational voltage 500 V. Latching endurance 15,000 cycles.

Frequently asked questions

What compliance documentation does this brand provide for 3VA1112-6MH36-0AF0?

As a Siemens SENTRON product, this MCCB carries the usual CE, UL, and IEC certifications for molded case circuit breakers. RoHS and REACH declarations are available from Siemens documentation. Specific approval markings are listed on the nameplate.

MPN
3VA1112-6MH36-0AF0