Skip to main content
Siemens 3VA1112-6MH36-0BH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1112-6MH36-0BH0 SENTRON MCCB, 125 A, 3-Pole, 220

MPN3VA1112-6MH36-0BH0

Siemens SENTRON 3VA1112-6MH36-0BH0, molded case circuit breaker, 3-pole, 125 A at 40 °C, interrupting rating 220 kA at 240 V, starter protection design with undervoltage release.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1112-6MH36-0BH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA11126MH360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1112-6MH36-0BH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C125 A
Current at 45 °C125 A
Current at 50 °C125 A
Current at 55 °C122 A
Current at 60 °C120 A
Current at 65 °C117 A
Current at 70 °C114 A
Switching capacity classH
Breaking capacity at 240 V220 kA
Breaking capacity at 415 V154 kA
Breaking capacity at 440 V75.6 kA
Breaking capacity at 500 V7.5 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.30.6 W
3VA1112-6MH36-0BH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM120M
Overcurrent protection functionI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1112-6MH36-0BH0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1112-6MH36-0BH0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionYes
Auxiliary CO contacts3
3VA1112-6MH36-0BH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1112-6MH36-0BH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

Siemens SENTRON 3VA1112-6MH36-0BH0 — 125 A MCCB with Starter Protection

Interrupting Capacity and Thermal Derating

The SCCR curve matters here: 220 kA at 240 V, 154 kA at 415 V, 75.6 kA at 440 V, and 7.5 kA at both 500 V and 690 V. That steep drop above 440 V tells you this breaker is optimized for 400 V-class systems (common in European and Asian industrial grids) — if your line runs at 480/500 V, the 7.5 kA rating still covers most transformer-fed faults but won't handle a direct utility tie without upstream current-limiting fuses. Thermal derating is gradual: 125 A holds steady from 40 °C through 50 °C, then drops to 122 A at 55 °C, 120 A at 60 °C, 117 A at 65 °C, and 114 A at 70 °C. Maximum power loss is 30.6 W at rated load, which factors into enclosure heat-budget calculations.

The 3VA1112-6MH36-0BH0 measures 70 mm deep, 76.2 mm wide, and 130 mm tall. That 76.2 mm (3 in) width is the standard 3-pole MCCB footprint for this current class — it fits existing SENTRON 3VA panel cutouts and busbar layouts without adapter plates. Depth of 70 mm clears most 200 mm-deep enclosures with room for rear-connected busbars or cable ladders. Rated insulation voltage is 800 V, and the operating temperature range spans -25 °C to 70 °C, with storage from -40 °C to 80 °C. The trip indicator and undervoltage release are factory-integrated into the basic switch (order code 3VA11126MH360AA0), so the complete unit arrives as one assembly — no loose accessory kits to track.

Frequently asked questions

What is the interrupting capacity of 3VA1112-6MH36-0BH0 at 415 V?

154 kA at 415 V. The full SCCR curve is: 220 kA at 240 V, 154 kA at 415 V, 75.6 kA at 440 V, and 7.5 kA at both 500 V and 690 V.

How do I get current pricing and availability for 3VA1112-6MH36-0BH0?

Submit an RFQ through this listing. Pricing and availability are confirmed at quote time against your quantity and delivery requirements — no published price here because market conditions vary.

What accessories are factory-installed on 3VA1112-6MH36-0BH0?

Factory-installed accessories include an undervoltage release (UVR), two auxiliary switches, and one trip alarm switch. The basic switch is order code 3VA11126MH360AA0.

What is the thermal derating curve for 3VA1112-6MH36-0BH0?

125 A from 40 °C to 50 °C, then 122 A at 55 °C, 120 A at 60 °C, 117 A at 65 °C, and 114 A at 70 °C. Maximum power loss is 30.6 W at rated load.

MPN
3VA1112-6MH36-0BH0