Skip to main content
Siemens 3VA1116-1AA32-0AA0 — Molded Case Circuit Breakers (MCCB)

3VA1116-1AA32-0AA0 SENTRON Switch Disconnector, 160 A, 3-Pol

MPN3VA1116-1AA32-0AA0
Active

Siemens SENTRON 3VA1 IEC frame 160, 3-pole switch disconnector, 160 A, SD100, without overload or short-circuit protection, busbar connection front terminal.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1116-1AA32-0AA0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
3VA1116-1AA32-0AA0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C160 A
Current at 45 °C160 A
Current at 50 °C160 A
Current at 55 °C158 A
Current at 60 °C155 A
Current at 65 °C153 A
Current at 70 °C150 A
Power loss, max.38 W
3VA1116-1AA32-0AA0 — Construction & Connection
ParameterValue
Main circuit connection typebusbar connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1116-1AA32-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Motor drive optionYes
Auxiliary CO contacts0
3VA1116-1AA32-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1116-1AA32-0AA0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.15 000
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens 3VA1116-1AA32-0AA0 is a SENTRON 3VA1 switch disconnector in an MCCB-style housing, rated 160 A continuous at 40 °C through 50 °C, with a modest derating curve to 150 A at 70 °C. The designation SD100 means it provides switch-disconnector function per IEC 60947-3 — it makes, carries, and breaks current under normal conditions and, importantly, provides visible isolation for safe maintenance access. This variant ships with busbar connection on the front terminals and includes a nut keeper kit for secure busbar mounting.

Above 50 °C the curve is gradual — 158 A at 55 °C, 155 A at 60 °C, 153 A at 65 °C, 150 A at 70 °C — so in a warm enclosure near a drive or transformer you lose only 10 A at the top of the operating range (-25 °C to 70 °C). Mechanical service life is 15 000 operating cycles typical, adequate for infrequent isolation duties but not for daily load-break switching. Front protection is IP40 — it keeps tools and fingers out but is not sealed against washdown.

Frequently asked questions

How do I get current pricing and availability for 3VA1116-1AA32-0AA0?

Current pricing and availability for the 3VA1116-1AA32-0AA0 are confirmed at quote time against an RFQ through our independent distribution channel. Submit an RFQ and we will return a firm quote with lead time based on real-time supply.

Will 3VA1116-1AA32-0AA0 drop into a panel specified around 3VA1112-5EE32-0AA0 without rewiring?

Both parts share the same 3VA1 MCCB housing and front-terminal busbar connection pattern, so the physical footprint and busbar interface are identical. The 3VA1116-1AA32-0AA0 is a switch disconnector (SD100) without protection electronics, while the 3VA1112-5EE32-0AA0 includes an electronic trip unit. They bolt into the same panel cutout and accept the same busbar kit, but the wiring for auxiliary signals differs because the SD100 has no auxiliary contacts or trip connections.

MPN
3VA1116-1AA32-0AA0