Skip to main content
Siemens 3VA1116-1AA32-0AC0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1116-1AA32-0AC0 SENTRON Switch Disconnector, 160

MPN3VA1116-1AA32-0AC0

Siemens SENTRON 3VA1116-1AA32-0AC0, switch disconnector in MCCB design, 3-pole, 160 A rated continuous current, IP40 front, busbar connection, 2 auxiliary switches HQ.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VA1116-1AA32-0AC0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
Product versionin MCCB design
3VA1116-1AA32-0AC0 — Ratings
ParameterValue
Number of poles3
Power loss, max.38 W
3VA1116-1AA32-0AC0 — Construction & Connection
ParameterValue
Main circuit connection typebusbar connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1116-1AA32-0AC0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1116-1AA32-0AC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1116-1AA32-0AC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens 3VA1116-1AA32-0AC0 is a SENTRON switch disconnector in a 3-pole MCCB-style housing, rated for 160 A continuous current. It is not a molded case circuit breaker — it provides no overload or short-circuit protection. Its job is safe isolation under load: you close it to pass power, open it to guarantee a visible air gap for lockout/tagout. The 160 A rating means it handles full-load current on a feeder or a large motor branch circuit, but the downstream protection devices handle the faults. Rated for AC operation up to 690 V and DC up to 500 V, it fits into 400 V and 690 V distribution panels common in European and IEC-spec installations. The 2 kA short-time withstand rating at 1 s and 0.5 s tells you the switch can survive a fault current of that magnitude while the upstream breaker clears — it is not a breaking device, but it must hold closed through the fault event.

The 3VA1116-1AA32-0AC0 shares the same 70 mm depth, 76.2 mm width, and 130 mm height as the 3VA1 frame breakers. That means it drops into the same panel cutout and busbar system as the SENTRON MCCBs — no re-drilling or adapter plates if you are swapping a breaker for a disconnect in an existing layout. Main circuit connection is via busbar on front terminals, so the bus stack runs across the front face, not the rear. No special sealing for washdown; keep it inside the enclosure.

Frequently asked questions

What is the difference between 3VA1116-1AA32-0AC0 and a molded case circuit breaker like 3VA1110-5ED36-0AC0?

The 3VA1116-1AA32-0AC0 is a switch disconnector with no overload or short-circuit protection — it isolates the circuit under load but does not trip on fault. The 3VA1110-5ED36-0AC0 is a full MCCB with a TM210 thermal-magnetic trip unit providing LI protection. Both share the same 3-pole frame, dimensions, and busbar connection pattern, so they are mechanically interchangeable in the panel. The choice depends on whether you need protection or just isolation.

Where can I buy 3VA1116-1AA32-0AC0?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the rated continuous current of 3VA1116-1AA32-0AC0?

The rated continuous current Iu is 160 A. This is the maximum current the switch can carry continuously without exceeding temperature limits.

Does 3VA1116-1AA32-0AC0 provide short-circuit protection?

No. It is a switch disconnector with no overload or short-circuit protection. It can withstand 2 kA for 1 s while an upstream device clears the fault, but it does not interrupt faults itself.

MPN
3VA1116-1AA32-0AC0