Skip to main content
Siemens 3VA1116-1AA32-0AF0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1116-1AA32-0AF0 SENTRON Switch Disconnector, 160

MPN3VA1116-1AA32-0AF0

Siemens SENTRON 3VA1 IEC frame 160, switch disconnector 3VA1116-1AA32-0AF0, 3-pole, In=160 A, without overload or short-circuit protection, busbar connection, front terminal, 1 auxiliary switch HQ + 1 trip alarm switch HQ.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3VA1116-1AA32-0AF0 — Identification
ParameterValue
Product designationSwitch disconnector
Brand / rangeSENTRON
Product versionin MCCB design
3VA1116-1AA32-0AF0 — Ratings
ParameterValue
Number of poles3
Power loss, max.38 W
3VA1116-1AA32-0AF0 — Construction & Connection
ParameterValue
Main circuit connection typebusbar connection
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1116-1AA32-0AF0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Motor drive optionYes
Auxiliary CO contacts2
3VA1116-1AA32-0AF0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1116-1AA32-0AF0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

Three poles, front-terminal busbar connection, and a 70 × 76.2 × 130 mm footprint that matches the 3VA1 molded-case breaker family, so it drops into the same panel cutout and busbar layout as a standard 3VA1 MCCB of the same frame.

Rated insulation voltage 800 V, max operational voltage 690 V AC 50/60 Hz and 500 V DC — covers standard 400/480 VAC industrial panels and 500 VDC battery or solar strings. IP40 on the front — suitable for general indoor panel use where no water jets or hose-down cleaning is expected. The auxiliary contact package (1 auxiliary switch HQ + 1 trip alarm switch HQ, 2 CO contacts total) gives you a status feedback pair for the PLC or indicator lamp: one NO/NC for the open/closed position, one for the trip/alarm state. Mechanical endurance rated at 15 000 operating cycles — typical for a switch disconnector in this class; fine for daily or weekly switching in a maintenance disconnect role, not intended for high-frequency motor starting.

Same 70 mm depth, 76.2 mm width, 130 mm height as the 3VA1 MCCB line — mounts on the same DIN rail or panel-mount adapter, connects via the same front-terminal busbar system. If you are swapping a 3VA1 breaker for this disconnect in an existing panel, the busbar drilling and terminal layout are identical; no rework on the copper. The busbar connection (nut keeper kit included per the description) saves time versus lug terminals on multi-pole runs.

Frequently asked questions

Where can I buy 3VA1116-1AA32-0AF0 and get a price?

This part is sourced and quoted to order through independent distribution. Submit an RFQ; availability and current pricing are confirmed at quote time.

Will 3VA1116-1AA32-0AF0 drop into a panel designed for 3VA1110-5EF32-0AM0 without rewiring?

Yes. Both parts share the same 70 × 76.2 × 130 mm footprint, 3-pole layout, front-terminal busbar connection, and SENTRON 3VA1 frame. The disconnect replaces the breaker in the same busbar drilling and DIN-rail position — no rewiring needed. The key difference: the 3VA1116-1AA32-0AF0 is a switch disconnector with no overcurrent protection, while 3VA1110-5EF32-0AM0 is a molded-case circuit breaker with a TM240 thermal-magnetic trip unit.

MPN
3VA1116-1AA32-0AF0